Installation & Operating Instructions
Owner’s Reference PowerPack 1500 MKII
2.6.4Setting of
Parameters
2.6.4.1Output
‘Frequency Setting
Press and hold the main on switch “I” for more than 3 seconds to turn on the right most LED. This indicates that the UPS is configured to work at 50Hz output frequency.
Press and hold the main switch “I” again for more than 3 seconds to configure the UPS to operate in the 60Hz mode.
Note: the battery backup mode output frequency will always follow the frequency of AC mains, even if the internal presetting is different.
50Hz60Hz
LED on continuously | LED flashing |