Capacity

 

1500 VA

 

 

 

Topology

 

Line-interactive

 

 

 

Input

•Nominal Voltage

•115V/230 Vac

 

•Voltage Range

•+/-25% (+/-20 or +/-30% Configurable)

 

•Frequency

•50/60Hz +/-5%

 

•Range

•>0.95 (full load condition)

 

•Power Factor

 

Output

•Nominal Voltage

•11 5Vac/230 Vac (100, 1 10, 120, 127V ac/208, 220, 230, 240 Vac Configurative)

 

•Voltage Regulation

•+10~15% (Line Mode typical), +3% (Battery back up mode)

 

•Frequency Stability

•50/60Hz +/-0.5%

 

•Wave form

•True Sine Wave

 

•Power Factor

•0.625 lagging to 1

 

•Distortion

• <5% (Linear Load)

 

•Overload Capacity

•110%~140% for 20 sec. (Back up mode)

 

 

•>104% for 10 cycles (Back up mode)

 

•Transfer Time

•<4mS (typical)

 

 

 

Battery

•Type

•Sealed, Maintenance-free Lead Acid

 

•DC Voltage

•24V dc

 

•Backup

•0~25 Minutes for standard Series

 

 

 

 

•Recharge Time

•<4 Hours Recovery to 90% (typical)

 

 

 

 

•External Battery

•Yes

 

Connector

 

 

•UsersReplacement

•Yes

 

 

 

Power Line

•Joules

•741 Joules

Surge Suppres-

•Max Peak Current

•1300A

sion

•Clamping Rating

•1300A (UL 1449 TVSS Rating)

 

•Response Time

•Normal Mode=OnS, Common Mode<1Ns

 

 

 

4826 Sterling Drive, Boulder, CO 80301

Specifications 30

PH: 720.406.8946 service@psaudio.com www.psaudio.com

 

©2009 PS Audio International Inc. All rights reserved.

Image 30
Contents Owner’s Reference IntroductionTable Of Contents Important Safety Instructions IntroductionSystem Descriptions Features Unpacking & Inspection Overview Box should include the followingGetting Started 5V Rear Panel Ventilation InstallationCharge the Battery Connect to ACConnect to PowerPlay Connect the LoadAC Mode On Battery ModeOperation and Functionality Test Manual Simulation of Power Outage for the UPS To conduct a simulation-testInstallation & Operating Instructions Setting Parameters Output ‘Frequency Setting Output ‘Frequency Setting Installation & Operating Instructions AVR Boost Range Setting Energy Saving mode Visual Indicators Audible / Visual Indicators Operating StatusLED1 LED2 LED3 LED4 LED5 LED6 Abnormal Status Indicators Screws Interface with PowerPlay Interface with PowerPlayWarranty WarrantyConditions Remedy Miscellaneous Outside the US If you require Service in NorthService AmericaYour serial ServiceIf you have problems Voltage changes Number Your purchase informationTroubleshooting TroubleshootingTroubleshooting Troubleshooting Specifications subject to change without prior notice Specifications Specifications