Page 28

®Troubleshooting

Owner’s Reference PowerPack 1500 MKII

Abnormal Situation

Cause

Solution

 

 

 

AC fail, the UPS fault LED

UPS is overloaded, UPS

Remove non-critical load and start the UPS again.

flashes, LED6 is lit.

shuts down in 20 sec-

 

 

onds in backup mode.

 

 

 

 

AC is normal, the UPS

UPS is overloaded.

Remove the non-critical loads.

fault LED flashes, LED6

 

 

is lit.

 

 

 

 

 

AC boost mode, the UPS

UPS is overloaded and

Remove the non-critical loads.

fault LED flashes, LED6

UPS will automatically

 

is lit.

turn off in 2 minutes.

 

 

 

 

Site Wiring fault LED is on

Site wiring problem.

Call an electrician to check your wiring.

communication function.

 

 

 

 

 

Not working

Wrong interface cable.

Purchase the correct one from your distributor.

LED 1,2,4 lit.

 

 

 

 

 

LED 1,2 lit.

UPS output circuit short.

Check output circuit.

 

 

 

LED 1,3 lit.

UPS inverter.

Call for service.

 

 

 

LED 1,4 lit.

Inverter over voltage.

Call for service.

 

 

 

LED 1,5 lit.

• UPS inverter is under

Remove the UPS to provide adequate air flow area,

 

voltage.

or check fan of UPS.

 

• UPS is over heated.

 

 

 

 

LED 1,3,5 lit.

 

Call for service.

 

 

 

LED 1,2,5 lit.

Charger over voltage.

Call for service.

 

 

 

LED1,4,5 lit.

Charger fault.

Plug in AC power.

 

 

 

 

Battery voltage abnormal

Refer to 4.2 instructions to replace batteries.

 

or the battery is dead.

 

 

 

 

It is suggested that the battery replacement should be conducted by an authorized technician and with the same type and capacity of battery.

4826 Sterling Drive, Boulder, CO 80301

Troubleshooting 28

PH: 720.406.8946 service@psaudio.com www.psaudio.com

 

©2009 PS Audio International Inc. All rights reserved.

Image 28
Contents Owner’s Reference IntroductionTable Of Contents Important Safety Instructions IntroductionSystem Descriptions Features Box should include the following Unpacking & Inspection OverviewGetting Started 5V Rear Panel Installation Charge the BatteryVentilation Connect to ACConnect to PowerPlay Connect the LoadOn Battery Mode AC ModeOperation and Functionality Test Manual Simulation of Power Outage for the UPS To conduct a simulation-testInstallation & Operating Instructions Setting Parameters Output ‘Frequency Setting Output ‘Frequency Setting Installation & Operating Instructions AVR Boost Range Setting Energy Saving mode Visual Indicators Audible / Visual Indicators Operating StatusLED1 LED2 LED3 LED4 LED5 LED6 Abnormal Status Indicators Screws Interface with PowerPlay Interface with PowerPlayWarranty WarrantyConditions Remedy Miscellaneous Outside the US Service in North ServiceIf you require AmericaService If you have problems Voltage changesYour serial Number Your purchase informationTroubleshooting TroubleshootingTroubleshooting Troubleshooting Specifications subject to change without prior notice Specifications Specifications