8300

8315 L&J Tankway Software Description

 

 

4.17 L&J MCG1000 Tank Gauge (LJ1000)

The LJ1000 point provides an interface to L & J MCG1000 Tank Gauge transmitters. This point provides both level and temperature data. Point and gauge status information is also available in this point block. This point executes on the Model 8315 Tank Gauge Interface module.

4.17.1Parameters

The database parameters used by the LJ1000 point are listed and described below:

Configuration

Function

Parameters

 

 

 

Tag

A Tag can contain 15 bytes of data and can include any printable ASCII

 

character. Tags can be used to identify the name of the tank being

 

monitored The default tag is set to “LJ1000.00”.

 

 

Description

A description can contain 30 bytes of data and can include any printable

 

ASCII character.

 

 

ID

Physical Address (0-127). The default is 0

 

 

DevType

Tank Gauge Type.

 

DevTypeTank Gauge Type.

 

DevType = 1 Uses a gray code table for CCW Varec gauges

 

DevType = 2 Uses a gray code table for CCW S&J gauges

 

DevType = 3 reports data in feet and hundredths of a foot

 

DevType = 4 reports data in 32nds of inches

 

 

Module

Physical address (1-4) of the Model 3215 used to interface to the tank

 

gauge transmitter. A value of 255 is undefined.

 

 

Filter

Gauge data filter constant. The Filter is used when scanning data from

 

an L&J gauge. A buffer is maintained for the last 8 readings. The Filter

 

determines how many of the reading in the buffer are used when

 

calculating the Level and Temp parameters. If all of the level readings

 

are within a deadband determined by the LJSCAN LevelDeadband

 

parameter, then the Level reading is updated with the latest data. If a

 

large change is detected (data changed more than the LevelDeadband),

 

then the Level is not updated until the change between readings is less

 

than the LevelDeadband. The default is 3.

 

 

TempDeadband

Change of State temperature deadband value. This parameter is used

 

when the Report is High or Low to determine if a change of state has

 

occurred. This parameter does not affect the Temp parameter value,

 

only if it is automatically sent to the Host system.

 

 

LevelDeadband

Change of State level deadband value. This parameter is used when the

 

Report is High or Low to determine if a change of state has occurred.

 

This parameter does not affect the Level parameter value, only if it is

 

automatically sent to the Host system.

 

 

Report

Causes automatic notification to the Host (in response to a Change of

 

State Request) when the Value Changes State. Parameter value can be

 

High, Low or No. Report=No disables notification. Points with Report =

 

High will be sent before points with Report = Low. The default is High.

 

 

53

Image 63
Contents Installation Operations Manual Page Copyright Disclaimer of Warranties Safety Precaution Definitions Safety Precautions Overview InstallationUsing ViewRTU Troubleshooting and maintenanceContents System Information SYS Using ViewRTU Troubleshooting Features VersionsApplications Operating temperature Specifications System DesignPower Supply Power consumptionStorage temperature HumidityMechanical Construction Overview TankGate Interface Hardware Motherboard Description Hardware Block DiagramTankGate motherboard Surge Protection Surge Gnd terminal block J4 Unit AC Input Power terminal block J2Field Power Vfield terminal block J3 Auxiliary DC Output Power terminal block J8Field Voltage Selection Jumper W3 AC Power Fuses F1,F2Switches and Indicators Reset push-button SW3Hard Reset 3.1 COM0 J7 Communications3.3 COM1 RS232/RS-485 Selection Switch SW2 3.4 COM1 Hardware Handshaking Switch SW13.2 COM1 RS-232/RS-485 J5 SW2 Set Tion Physical Handshak Ting Layer Ing Communica HardwareWith RTS / CTS RS-232J6 TankGate Communications Cable8315 L&J Tankway Interface Module Model 8315 TankGate DescriptionLED Indicators D1-D6 ID DIP Switch SW1Surge/Shield Ground Connector J4 External Power Connector +48V J2Connect the field wiring Field Wiring terminal block J38315 L&J Tankway Interface Module TankGate Interface Software Features Real-Time / Multitasking Executive Automatic Fault RecoveryReal-Time Clock System Tasks ProtocolsData Scanning Task Database ManagerTankGate 8315 Software Blocks TankGate Software BlocksParameter Classes Database OrganizationPoint Format Parameter DescriptionParameter Data Formats Common ParametersData Format Description Value Parameter PntCheckSum ParameterPntStatus Parameter Elapse ParameterChange of State-Related Parameters Gathering Point DataStandard Request-Response Format Change of State FormatDeadband Modbus Slave Modbus CommunicationsFixed Modbus Map Function Code Description CommentsAddress Type Number Parameter Data Type Gwblk method 8315 L&J Tankway Software Description TankGate Interface Data Address Parameter Comments Dynamic Parameters Function Configuration Parameters FunctionClock CLK ParametersCommunications COM Configuration Function ParametersApplication Floating Point Register Fpreg Dynamic Function ParametersReal 4 bytes value API Emulator EMUByte value indicating status of point Values are Hex representation of the request sent by the host Configuration Parame Function TersCurrent Command EMU Gateway EmugwDisplays the tank number of the currently selected tank Gauging Systems Inc. Model 2000 Interface GS2000 Last message. The maximum is 255 seconds. The default is Raw2 Gateway Block Gwblk Addr1 is the Data Address and PntRef1 is the corresponding Byte value indicating status of point Values are No errorCRC-16 Checksum of points static Configuration Parameters Size ParameterInteger 2 bytes value Integer Register IregCurrent request message, displayed in hex format Modbus Gateway ModgwCurrent command. Values include Value = Ax + By + Cz + K Scaler Point ScalerDynamic Parame Function Ters Output value for the Scaler pointValue parameter converted to Integer format System Information SYS 17 L&J MCG1000 Tank Gauge LJ1000 PntStatus will be set to indicate the failure Application 18 L&J MCG1500 Tank Gauge LJ1500 Task on the Motherboard determines that the Model 8315 has 8315 L&J Tankway Software Description TankGate Interface 19 L&J MCG2000 Tank Gauge LJ2000 Enables the watchdog task on the Motherboard. The watchdog 8300 20 L&J Scanner Ljscan Command currently being sent to the gaugeNumber of gauge polls since last reset Number of gauge polls which resulted in an errorOut 8315 L&J Tankway Software Description TankGate Interface Installation Safety Guidelines General Safety GuidelinesInstallation Mounting the TankGate inside the enclosure Mounting the TankGateSelect the Unit address Wiring Up PowerInstalling Communications Mounting the EnclosureEstablishing Host Communications Power-UpRS-485 Communications Initial system verificationInstallation TankGate Interface Executing ViewRTU Installing ViewRTUOverview System RequirementsViewRTU Version Selection dialog ViewRTU window ViewRTU Menu BarFile Menu Point Menu Select Point to Add dialog box EditEdit Point selection dialog Edit Point dialog DeletePoint deletion dialog Config Menu Download Database to RTUUpload Database from TankGate Creating a Password To enter the passwordCommunications Menu Changing the PasswordChanging the Password PC SetupStatus Port Communications Setup dialogOptions Menu ConnectTankGate search dialog Import All Convert Configuration FilesConvert ViewRTU versions dialog Export AllHelp Menu Using ViewRTUConfiguring Single Points Edit Digital Point dialog Edit Point Window Push-buttonsMinimize Previous Minimizing the Edit Point WindowConnections NextEdit point parameter value dialog To modify a ValueUpload To modify a valueAdding Multiple Points Configuring Multiple PointsTo modify a Reference Edit point parameter reference dialogAdding Multiple Points Spreadsheet ModePaste Point MenuEdit Menu CopyPaste & Dnld Set ValueSet Value with Auto Increment Options Menu ImportExport View Hide Row/ColParameter Type Description Unhide All Creating and Editing ConnectionsDisplaying the Point Connections window Point Connections WindowTo create a Connection Using ViewRTU TankGate Interface Indicator Condition Run indicator1.3 TXD/RXD LEDs Using the TankGate Push-buttonsCommunications indicator LED Displays under Abnormal ConditionsPress the Reset button Performing a Hard ResetSet the ID DIP switch to the desired addresses Replacing a defective component or module MaintenanceTroubleshooting TankGate Interface 102 Ordering Structure Nema 4 Enclosure Ordering Structure Remote Terminal Unit TankGateModbus Map Value12 Fpreg 3034 3094 8300 Your official representative Your offical representative