8315 L&J Tankway Software Description | TankGate Interface |
|
|
4.11 Gauging Systems Inc. Model 2000 Interface (GS2000)
The GS2000 point provides an interface to GSI 2000 Tank Gauge transmitters. This point provides both level and temperature data. Point and gauge status information is also available in this point block. This Software Block executes on the Model 8210 Mark/Space Interface Module.
4.11.1Parameters
The database parameters used by the GS2000 point are listed and described below:
Configuration | Function |
|
Parameters |
|
|
|
| |
Tag | The point description can contain 30 bytes of data and can include any | |
| printable ASCII character. Descriptions can be used as information | |
| relevant to any aspect of the point, such as its use, location, operating | |
| information, etc. The default description is set to “GS200.00”. | |
|
| |
Description | The point description can contain 30 bytes of data and can include any | |
| printable ASCII character. Descriptions can be used as information | |
| relevant to any aspect of the point, such as its use, location, operating | |
| information, etc. The default description is set to “GS200.00”. | |
|
| |
FastScanMode | Places the GS2000 point in the Fast Scan mode. Values are Enable or | |
| Disable. |
|
|
| |
ID | Physical Address of the tank gauge transmitter | |
|
|
|
Module | Not used. |
|
|
| |
SpeedMode | Allows user to set the speed mode. Selections include High, Low or | |
| Undefined. |
|
|
| |
DataMode | Data format of the transmitter encoder. Values are: | |
| 0: Fractional | |
| 1: Decimal | |
| 2: Metric | |
| 3: Metric | |
|
| |
LevelDeadband | Specifies the amount of change in the Level that must occur for the | |
| Value to be updated each Change of State period. The default is 0. | |
|
| |
LevelOffset | Specifies the amount of offset to add to the Level. The default is 0. | |
|
| |
TempMode | Allows the user to enable or disable the temperature mode or specify | |
| the temperature format. Values are: | |
| F: Fahrenheit (Model 1900 Emulator) | |
| C: Celsius | (Model 1900 Emulator) |
| 3: Fahrenheit (Model 1800 Emulator) | |
| 4: Celsius | (Model 1800 Emulator) |
| 5: Fahrenheit (Model 1800 Emulator) | |
| 6: Celsius | (Model 1800 Emulator) |
| U: Undefined - Assumes transmitter does not support temperature. | |
|
| |
TempDeadband | Specifies the amount of change in the Temp that must occur for the | |
| Value to be updated each Change of State period. The default is 0.25. | |
|
|
|
42 | Installation and Operations Manual |