| Configuration | Function |
|
| Parameters |
|
|
|
|
|
|
| TempOffset | Specifies the amount of offset to add to the Temp. The default is 0. |
|
|
|
|
|
| Report | Causes automatic notification to the Host (in response to a Change of |
|
|
| State Request) when the Value changes State. Parameter value can be |
|
|
| High, Low or No. Report=No disables notification. Points with Report = |
|
|
| High will be sent before points with Report = Low. The default is High. |
|
|
|
|
|
| Maxtime | Specifies the maximum time (in secs) between automatic Change of |
|
|
| State responses being sent to the Host. Report must be set to either |
|
|
| Low or High for the Value parameter to be sent in response to a Change |
|
|
| of State Request. A value of 0 disables this option. |
|
|
| cause responses to be sent even if the value has not changed since the |
|
|
| last message. The maximum is 255 seconds. The default is 60. |
|
|
|
|
|
Dynamic Parameters | Function |
|
|
Level | Floating point value representing the tank level. The Level will be |
| presented in decimal feet or meters, depending upon the LevelConvert |
| parameter of the |
| WVSCAN point. |
|
|
Temp | Floating point value representing the tank temperature. The |
| Temperature will be presented in Fahrenheit or Celsius, depending |
| upon the TempConvert parameter of the WVSCAN point |
|
|
Alarm | Gauge Alarms. Not used for the GS2000 point. |
|
|
PntStatus | Integer HEX value indicating status of point. Values are: |
| 0x0001: Gauge Not Responding. The first time the gauge does not |
| respond, the 0x08 bit is set. On the second try, the 0x01 bit is set. |
| 0x0002: Parity Error on last scan |
| 0x0004: Data from the Gauge is Not Valid |
| 0x0008: Timeout Error. The Motherboard monitors the Elapse |
| parameter. If data is not being updated (due to the 8210 |
| malfunctioning), the 0x08 bit will be set. |
| 0x0010: Gauge did not respond on last scan |
| 0x0020: Invalid Level |
| 0x0040: Large change in Level or Temperature |
| 0x0800: Mark Line shorted to ground |
| 0x0400: Space Line shorted to ground |
| 0x0200: Blown Fuse |
| 0x0100: No +48 VDC |
|
|
GaugeStatus | Byte value indicating status of the gauge. Refer to the transmitter |
| manual for details on the GaugeStatus |
| 0x01: Temperature is out of Range |
| 0x04: Temp Sign |
| 0x08: X100 Temp bit |
|
|
Elapse | Time of the last Change of State |
|
|
PntCheckSum | |
|
|
Raw1 | Raw data from gauge. Value reported as hexidecimal value. |
|
|
43