8315 L&J Tankway Software Description | TankGate Interface |
|
|
4.20 L&J Scanner (LJSCAN)
The L&J Scanner point is used in conjunction with L&J Tank (LJ1000, LJ1500 and LJ2000) gauge points. This point provides dynamic and statistical data for the Model 8315 tank gauge interface module and L&J tank transmitters.
4.20.1Parameters
The database parameters used by the LJSCAN point are listed and described below:
Configuration | Function |
Parameters |
|
|
|
Module | Model 8215 module address |
|
|
MaxRetry | Value between |
| attempt to poll a tank transmitter that has not responded. Default is 2. |
|
|
Timeout | Value between |
| scanner will wait for a response from a tank transmitter. Default is |
| 2000. |
|
|
ScanDelay | Value between |
| scanner will delay between each poll. Default is 500. |
|
|
LevelConvert | Determines the units in which the level data will be displayed. F: feet, M: |
| Meters m: Millimeters. |
|
|
TempConvert | Determines the units in which the temperature data will be displayed. F: |
| Fahrenheit, C: Celsius. |
|
|
LevelFilter | Value used by LJ1000, LJ1500 and L2000 points for filtering level |
| changes |
|
|
TempFilter | Value used by LJ1000, LJ1500 and LJ2000 points for filtering |
| temperature changes |
|
|
HoldOff | Gauge down holdoff count. The HoldOff is used to reduce the number |
| of scan requests issued to a gauge that is not responding. |
|
|
ScanTimeout | Time value used to set an alarm bit in the PntStatus parameter of |
| LJ1000, LJ1500 and LJ2000 points for gauges that are not responding or |
| responding with errors. |
|
|
Dynamic Parameters | Function |
|
|
ID | Address of gauge currently being scanned |
|
|
Cmd | Command currently being sent to the gauge |
|
|
Pnt | Point currently being executed |
|
|
NumRequests | Number of gauge polls since last reset |
|
|
NumComErrors | Number of gauge polls which resulted in an error. |
|
|
62 | Installation and Operations Manual |