Varec 8315 Series manual Troubleshooting TankGate Interface 102

Page 112

Troubleshooting

TankGate Interface

 

 

102

Installation and Operations Manual

Image 112
Contents Installation Operations Manual Page Copyright Disclaimer of Warranties Safety Precaution Definitions Safety Precautions Installation Using ViewRTUTroubleshooting and maintenance OverviewContents System Information SYS Using ViewRTU Troubleshooting Versions FeaturesApplications Specifications System Design Power SupplyPower consumption Operating temperatureHumidity Storage temperatureMechanical Construction Overview TankGate Interface Hardware Hardware Block Diagram Motherboard DescriptionTankGate motherboard Unit AC Input Power terminal block J2 Field Power Vfield terminal block J3Auxiliary DC Output Power terminal block J8 Surge Protection Surge Gnd terminal block J4AC Power Fuses F1,F2 Field Voltage Selection Jumper W3Reset push-button SW3 Switches and IndicatorsHard Reset Communications 3.1 COM0 J73.4 COM1 Hardware Handshaking Switch SW1 3.3 COM1 RS232/RS-485 Selection Switch SW23.2 COM1 RS-232/RS-485 J5 Communica Hardware SW2 Set Tion Physical Handshak Ting Layer IngTankGate Communications Cable With RTS / CTS RS-232J68315 L&J Tankway Interface Module Description Model 8315 TankGateID DIP Switch SW1 LED Indicators D1-D6External Power Connector +48V J2 Surge/Shield Ground Connector J4Field Wiring terminal block J3 Connect the field wiring8315 L&J Tankway Interface Module TankGate Interface Automatic Fault Recovery Software Features Real-Time / Multitasking ExecutiveReal-Time Clock Protocols Data Scanning TaskDatabase Manager System TasksTankGate Software Blocks TankGate 8315 Software BlocksDatabase Organization Point FormatParameter Description Parameter ClassesCommon Parameters Parameter Data FormatsData Format Description PntCheckSum Parameter PntStatus ParameterElapse Parameter Value ParameterGathering Point Data Standard Request-Response FormatChange of State Format Change of State-Related ParametersDeadband Modbus Communications Modbus SlaveFunction Code Description Comments Fixed Modbus MapAddress Type Number Parameter Data Type Gwblk method 8315 L&J Tankway Software Description TankGate Interface Data Address Parameter Comments Configuration Parameters Function Clock CLKParameters Dynamic Parameters FunctionConfiguration Function Parameters Communications COMApplication Dynamic Function Parameters Floating Point Register FpregReal 4 bytes value Emulator EMU APIByte value indicating status of point Values are Configuration Parame Function Ters Current CommandEMU Gateway Emugw Hex representation of the request sent by the hostDisplays the tank number of the currently selected tank Gauging Systems Inc. Model 2000 Interface GS2000 Last message. The maximum is 255 seconds. The default is Raw2 Gateway Block Gwblk Byte value indicating status of point Values are No error CRC-16 Checksum of points static Configuration ParametersSize Parameter Addr1 is the Data Address and PntRef1 is the correspondingInteger Register Ireg Integer 2 bytes valueModbus Gateway Modgw Current request message, displayed in hex formatCurrent command. Values include Scaler Point Scaler Dynamic Parame Function TersOutput value for the Scaler point Value = Ax + By + Cz + KValue parameter converted to Integer format System Information SYS 17 L&J MCG1000 Tank Gauge LJ1000 PntStatus will be set to indicate the failure Application 18 L&J MCG1500 Tank Gauge LJ1500 Task on the Motherboard determines that the Model 8315 has 8315 L&J Tankway Software Description TankGate Interface 19 L&J MCG2000 Tank Gauge LJ2000 Enables the watchdog task on the Motherboard. The watchdog 8300 Command currently being sent to the gauge Number of gauge polls since last resetNumber of gauge polls which resulted in an error 20 L&J Scanner LjscanOut 8315 L&J Tankway Software Description TankGate Interface General Safety Guidelines Installation Safety GuidelinesInstallation Mounting the TankGate Mounting the TankGate inside the enclosureWiring Up Power Installing CommunicationsMounting the Enclosure Select the Unit addressPower-Up RS-485 CommunicationsInitial system verification Establishing Host CommunicationsInstallation TankGate Interface Installing ViewRTU OverviewSystem Requirements Executing ViewRTUViewRTU Version Selection dialog ViewRTU Menu Bar ViewRTU windowFile Menu Point Menu Edit Select Point to Add dialog boxEdit Point selection dialog Delete Edit Point dialogPoint deletion dialog Download Database to RTU Config MenuUpload Database from TankGate To enter the password Creating a PasswordChanging the Password Changing the PasswordPC Setup Communications MenuPort Communications Setup dialog StatusConnect Options MenuTankGate search dialog Convert Configuration Files Convert ViewRTU versions dialogExport All Import AllUsing ViewRTU Help MenuConfiguring Single Points Edit Point Window Push-buttons Edit Digital Point dialogMinimize Minimizing the Edit Point Window ConnectionsNext PreviousTo modify a Value UploadTo modify a value Edit point parameter value dialogConfiguring Multiple Points To modify a ReferenceEdit point parameter reference dialog Adding Multiple PointsSpreadsheet Mode Adding Multiple PointsPoint Menu Edit MenuCopy PasteSet Value Paste & DnldSet Value with Auto Increment Import Options MenuExport Hide Row/Col ViewParameter Type Description Creating and Editing Connections Unhide AllPoint Connections Window Displaying the Point Connections windowTo create a Connection Using ViewRTU TankGate Interface Run indicator Indicator ConditionUsing the TankGate Push-buttons Communications indicatorLED Displays under Abnormal Conditions 1.3 TXD/RXD LEDsPerforming a Hard Reset Press the Reset buttonSet the ID DIP switch to the desired addresses Maintenance Replacing a defective component or moduleTroubleshooting TankGate Interface 102 Ordering Structure Remote Terminal Unit TankGate Ordering Structure Nema 4 EnclosureModbus Map Value12 Fpreg 3034 3094 8300 Your official representative Your offical representative