8315 L&J Tankway Software Description | TankGate Interface |
| |
|
|
|
|
|
|
|
|
| Configuration Parameters | Function |
|
|
|
|
|
| Maxtime | Specifies the maximum time (in secs) between automatic Change |
|
|
| of State data being sent to the Host in response to a Change of |
|
|
| State Request. Report must be set to either Low or High for the |
|
|
| Value parameter to be sent in response to a Change of State |
|
|
| Request. A value of 0 disables this option. |
|
|
| cause responses to be sent even if the value has not changed |
|
|
| since the last message. The maximum is 255 seconds. The |
|
|
| default is 240. |
|
|
|
|
|
| Watchdog | Enables the watchdog task on the Motherboard. The watchdog |
|
|
| task monitors the LJ2000 point on the Model 8315 and verifies it |
|
|
| is scanning for gauges. If the Model 8215 fails, the 0x4000 and |
|
|
| the 0x0010 bits of the PntStatus will be set to indicate the failure. |
|
|
|
|
|
Dynamic Parameters | Function |
|
|
Level | Floating point value representing the tank level (in feet). |
|
|
Temp | Floating point value representing the tank temperature (in |
| Fahrenheit). |
|
|
PntStatus | Integer HEX value indicating status of point. Values are: |
| 0x0002: Scan Timeout |
| 0x0010: Gauge Not Responding |
| 0x0020: Blown Transmit Fuse |
| 0x0040: Parity Error |
| 0x0080: Tankway Error |
| 0x4000: Failure of the Model 8315. This bit is set if the |
| Watchdog task on the Motherboard determines that the Model |
| 8315 has stopped updating. |
|
|
GaugeStatus | Byte value indicating status of the gauge. |
|
|
AlarmTime | Time that alarm first occurred. The point is in alarm when the |
| PntStatus is non zero. |
|
|
Elapse | Time of the last scan. |
|
|
ScanTime | Time of the last good reading. A reading is considered good if it |
| has no parity or |
|
|
Raw1 | Raw data from gauge. Value reported as hexadecimal value. |
|
|
Raw2 | Raw data from gauge. Value reported as hexadecimal value. |
|
|
PntCheckSum | |
|
|
4.19.2Application
The LJ2000 point provides an interface to L&J MCG2000 Gauges. L&J Model 2000 Gauges are connected directly to a Model 8315 Tank Gauge Interface Module. The Model 8315 is automatically detected at startup, and an LJSCAN point is automatically created to manage the scanning task. The Module parameter determines which Model 8315 will be used. The ID must match the unit address of the MCG2000.
60 | Installation and Operations Manual |