Nortel Networks NN44200-300 manual Inspecting the server interior, To inspect the server interior

Page 29

Inspecting the server interior 29

2Loosen the three thumbscrews at the rear of the top cover.

3Remove the server cover by pulling the cover toward the rear of the chassis, and then lifting it up and off.

4Clip the lead from your ESD wrist strap to an unpainted metal section of the chassis.

—End—

What is next?

Continue with "Inspecting the server interior" (page 29).

Inspecting the server interior

Introduction

You should perform a visual inspection for loose components, foreign matter, or shipping damage inside the server.

CAUTION

When working with interior components, use an ESD wrist strap to protect static-sensitive components.

To inspect the server interior

Step Action

1Carefully check all the cards to ensure they are fully seated on the baseboard.

2Check for any loose wires or foreign objects, such as loose screws, inside the chassis.

3Review the slot locations (see "Slot assignments" (page 15)).

4Do one of the following:

IF

THEN

you observe any damage

contact your Nortel technical

 

support representative.

 

 

Nortel CallPilot

1002rp Server Hardware Installation

NN44200-300 01.01 Standard

5.0 23 February 2007

Copyright © 2007, Nortel Networks

Nortel Networks Confidential

Image 29
Contents 1002rp Server Hardware Installation Trademarks Japan Vcci statement Information for JapanJapan Denan statement Page February Publication HistoryPublication History Contents Contents Getting help from the Nortel Web site Getting help over the phone from a Nortel Solutions CenterGetting help through a Nortel distributor or reseller Server dimensions and weight Server featuresThis chapter IntroductionEnvironmental specifications Front panel features front view without the front bezelRear panel diagram Alarm boardOverhead view of empty server showing PCI and ISA connectors Reference Documents Slot assignments1002rp server description T1/SMDI Slot definition and slot numberingBRD20 Network connectivitySample network setup Communication Server Sample network setup MeridianCallPilot Elan subnet and Nortel server subnet setup Switch connectivityMeridian 1 or Communication Server 1000 systems Network requirementsSupported peripheral devices Remote access connectivityDeviceDescription Installation checklist Installation overviewPreparing for installation Conventions for warnings To unpack the equipment Unpacking the 1002rp serverTo remove the front bezel What is next?Removing the front bezel and server cover Remove the front bezel see To remove the front bezel To remove the server coverTo inspect the server interior Inspecting the server interiorInstallation and Configuration To replace the front bezel after installation is completeEnd Preparing for installation Equipment handling guidelines Safety precautionsSafety information AC versus DC systems Installing the second power supply module AC or DCAbout the power supply module To install the power supply module AWG DC wire gauge tablesDC rack cabling Metric wire conversionPower supply installation Rack power and grounding DC power distribution rationale About the power distribution unitPDU power and grounding Multiple PDUsDC power input PDU terminal blocks and wiring diagramTo bring DC power and ground into the PDU Bringing power and ground into the PDUTo install the server Installing the serverRequired equipment Modem DIP switchesPreparing the modem DIP To set the modem DIP switchesContinue with Connecting peripherals to the server Connecting peripherals to the server To connect the modem to the server To connect the server to the Elan subnet Connecting the server to the Elan subnetMedia Access Control address Server will To connect the server to the Nortel server subnet Connecting the server to the Nortel server subnet optionalRequirements Installing the Nortel software feature dongleTo install the software feature dongle Before you begin Connecting the server to powerPlug the server AC power cord into the server rear panel To connect the 1002rp AC server to powerTo connect the 1002rp DC server to power To start the server Copyright 2007, Nortel Networks Ferrites secured to an external cable Index Index Tlan Index Page 1002rp Server Hardware Installation