MGE UPS Systems 4.5 kVA, 6 kVA, 9 kVA Failure of AC input power and operation on battery power

Page 20

3. Operation

3.4 Failure of AC input power and operation on battery power

AC input power is not available, the battery steps in to supply the protected equipment.

Transfer to battery power

bypass

20

When AC-power source goes outside tolerances or fails completely, LED 20 goes ON and the buzzer beeps three times.

Threshold for the low-battery shutdown warning

bypass

20

The low-battery shutdown warning threshold can be set by the user, with the "UPS Driver" software (default setting equal to 20% of full backup time).

LED 20 flashes when the setted level is reached.

The buzzer beeps every three seconds when less than 10% of backup time remains.

There is very little remaining battery backup time. Close all applications because UPS automatic shutdown is imminent.

End of backup time

bypass

The buzzer sounds continuously.

Press button 16 to turn the buzzer OFF.

16

The equipment is no longer supplied with power.

Sleep mode

This operating mode may be personalized using the "UPS Driver" software (see section 3.5).

It saves battery power when no equipment is connected to the UPS. Shutdown occurs after 5 minutes. The UPS automatically restarts when the AC-power source returns to within tolerances.

Return of AC input power

If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function (activated by return of AC input power) has not been disabled (see section 3.5).

Page 20 - 51033212EN/AC

Image 20
Contents Installation Comet EXtremeIntroduction Pictograms Using this documentForeword Contents Failure of AC input power and operation on battery power Glossary IndexPresentation Comet EXtreme range6 kVA tower models 6 kVA rack models12 kVA tower models 12 kVA rack models Comet EXtreme 9 and 12 kVA BackComet EXtreme 4.5 and 6 kVA EPO Emergency Power Off Battery extensions for UPS backup times of 80 minutesBattery extensions for 4.5 or 6 kVA Comet EXtreme OptionsBattery extensions for 9 or 12 kVA Comet EXtreme CLAAlarms Battery Load Remaining Control panelUnpacking and checks InstallationElectronic module Battery module Electronic module Installation of the rack version Rack mounting diagram with railsBattery-module connections Check that the battery circuit breaker 2 is OFFInstallation of the communications-card option Connection to the RS 232 communications port optionalAlways connect the earthing wire first Connection to the connection modulesON-LINE operating mode OperationBargraph indications When button 15 is pressedStart-up Failure of AC input power and operation on battery power Personalizable function Default setting PersonalizationFunction On / OFF conditions tabBattery tab Personalizable function Default setting OptionsOutput tab By-pass tabConnected equipment is no longer supplied with power ShutdownMaintenance TroubleshootingFrench Training Center on Montbonnot site USA Training Center on Costa Mesa siteMaintenance Replacement of the electronic module Disconnecting the connection moduleReconnecting the connection module Connected equipment is again protected by the UPSUPS recycling at the end of service life EnvironmentThis product has been designed to respect the environment PackingON-LINE mode AppendicesGlossary Manual bypassSleep mode Start on battery powerTolerance for AC-power Out of toleranceIndex UPS Driver32 51033212EN/AC