MGE UPS Systems 9 kVA, 4.5 kVA, 6 kVA, 12 kVA user manual Battery tab, Output tab, By-pass tab

Page 22

3. Operation

"Battery" tab

 

Personalizable function

Default setting

Options

 

 

 

 

 

 

 

Once a week

 

"Battery test" intervals

Every day

Once a month

 

 

 

No test

 

 

 

 

 

"Low-battery shutdown warning" threshold

20% remaining battery

40% remaining battery

 

 

backup time

backup time

 

 

 

 

 

Charger

Standard

CLA (2, 4 or 8 hours)

 

 

 

 

"Output" tab

Rated AC-power source voltage (see figure 1)

230 V

200 V-208 V-220 V-240 V

 

 

 

Rated AC-power source frequency

50 Hz

60 Hz

 

 

 

Tolerance for AC-power source frequency

± 5%

± 1% to ± 10% , in 1% steps

 

 

 

Alarm threshold for overload

100%

0 to 100%, in 10% steps

 

 

 

Restart inverter after short circuit

Disabled

Enabled (click to add check)

 

 

 

"By-pass" tab

Authorized voltage range for transfer to bypass

187 V to 265 V (for

187 V to 265 V,

if fault or overload

230 V rated voltage)

in 1V steps

 

 

 

Authorized frequency range for transfer to bypass

± 10%

± 1% to ± 10%, in 1% steps

if fault or overload

 

 

 

 

 

Transfer to bypass if overload

Enabled

Disabled (click to remove check)

 

 

 

Transfer to bypass following a fault, whatever

Disabled

Enabled (click to add check)

the conditions on the AC-power source

 

 

 

 

 

The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).

100%

95%

90%

66%

50%

Available power as a percentage of the rated power

84

Voltage in V

Fig. 1

Page 22 - 51033212EN/AC

Image 22
Contents Installation Comet EXtremeIntroduction Foreword Using this documentPictograms Contents Failure of AC input power and operation on battery power Glossary Index6 kVA tower models PresentationComet EXtreme range 6 kVA rack models12 kVA tower models 12 kVA rack models Comet EXtreme 4.5 and 6 kVA BackComet EXtreme 9 and 12 kVA Battery extensions for 4.5 or 6 kVA Comet EXtreme EPO Emergency Power OffBattery extensions for UPS backup times of 80 minutes OptionsBattery extensions for 9 or 12 kVA Comet EXtreme CLAAlarms Battery Load Remaining Control panelElectronic module Battery module InstallationUnpacking and checks Electronic module Installation of the rack version Rack mounting diagram with railsBattery-module connections Check that the battery circuit breaker 2 is OFFInstallation of the communications-card option Connection to the RS 232 communications port optionalAlways connect the earthing wire first Connection to the connection modulesON-LINE operating mode OperationStart-up When button 15 is pressedBargraph indications Failure of AC input power and operation on battery power Function Personalizable function Default settingPersonalization On / OFF conditions tabOutput tab Battery tabPersonalizable function Default setting Options By-pass tabConnected equipment is no longer supplied with power ShutdownFrench Training Center on Montbonnot site MaintenanceTroubleshooting USA Training Center on Costa Mesa siteMaintenance Replacement of the electronic module Disconnecting the connection moduleReconnecting the connection module Connected equipment is again protected by the UPSThis product has been designed to respect the environment UPS recycling at the end of service lifeEnvironment PackingGlossary ON-LINE modeAppendices Manual bypassTolerance for AC-power Sleep modeStart on battery power Out of toleranceIndex UPS Driver32 51033212EN/AC