4. Maintenance
4.2 Replacement of the electronic module
Disconnecting the connection module
Before turning the switch,
see the manual
NORMAL |
1. | Turn the manual bypass switch 7 , located behind the UPS |
(see section 1.2), from the NORMAL to the intermediate | |
position. | |
2. | Check that LED 18 is ON before continuing to the BYPASS |
position. |
bypass
7
18
If LED 18 is not ON, do not switch to the BYPASS position and call the
3.Turn the manual bypass switch 7 from the intermediate position to the BYPASS position.
The connected equipment is supplied by the AC- power source, via the manual bypass.
21
Before turning the switch,
see the manual
NORMAL |
4.Shut down the UPS by pressing button 21 (return to the OFF position).
5.Switch the battery circuit breaker(s) 2 to the OFF position.
6.Remove the two fixing screws 30 to free the connection module 8 (see next page).
7.Remove the connection cable(s) from the battery module(s).
The UPS can be replaced. The connected equipment is supplied by the
Page 26 - 51033212EN/AC