6.1 Glossary
Authorized voltage range for transfer to bypass if fault or overload
Automatic bypass
Automatic start following return of AC input power
Backup time
Bargraph
Battery test
Cold start
Connection module
Dialog box
Double conversion
Equipment
Forced shutdown
6. Appendices
Upper and lower voltage thresholds within which the UPS can operate on the automatic bypass in the event of a UPS fault or overload.
Automatic switch controlled by the UPS, used to connect the equipment directly to the
When AC input power returns following shutdown at the end of the battery backup time, UPS automatic start can be enabled or disabled.
Time that the connected equipment can operate on battery power.
Device on the front panel indicating the percent remaining backup time or the percent load.
Internal UPS test on battery status.
See "Start on battery power".
Unit grouping the receptacles for connection to the
A window in a computer program displayed for selection by the user of various options and parameter settings.
The power supplied to the connected equipment is completely regenerated by continuous double conversion, i.e. the AC power from the
Devices or systems connected to the UPS output.
Allows a "clean" of computer operating systems depending on the low battery threshold setting. If the input source is restored during the time period between the shutdown order and actual system shutdown, it causes a voluntary interruption of the supply of power to the connected equipment (lasting 10 seconds) after system shutdown.
Manual bypass | Rotary switch controlled by the user, used to connect the equipment directly |
| to the |
| UPS maintenance or replacement, without interrupting the supply of power |
| to the connected equipment. |
| The normal UPS operating mode, by which the |
| the UPS, which in turn, following double conversion of the AC power, |
| supplies the connected equipment. |
51033212EN/AC - Page 29