American Power Conversion PD60G6FK1, PD60F6FK1, PD60L6FK1 PDU Alarms, Alarm Condition Explanation

Page 32

PDU Display Interface

PDU Alarms

This table lists all alarms that can be generated by the PDU, as displayed by the All Possible Alarms option, with numeric variables between the < > characters. Logged alarms will display specific numbers instead.

Alarm Condition

Explanation

 

 

Input V <Ln-N> =<Value>

Input voltage of the phase indicated has dropped below the

Voltage Under Limit

configured lower limit.

 

 

Input V <Ln-N> =<Value>

Input voltage of the phase indicated exceeded the configured

Voltage Over Limit

upper limit.

 

 

Output V <Ln-N> =<Value>

Phase-to-neutral output voltage for phase <L-N> dropped below

Voltage Under Limit

the configured limit.

 

 

Output V <Ln-N>=<Value>

Phase-to-neutral output voltage for phase <L-N> exceeded the

Voltage Over Limit

configured limit.

 

 

Output I L<n>=<Value>

Current of output phase <N> exceeded the configured limit.

Current Over Limit

 

 

 

Output I L<n>=<Value>

Current of output phase <N> dropped below the configured limit.

Current Under Limit

 

 

 

Output Neut=<Value>

Current on the neutral wire for the output phases exceeded the

Current Over Limit

configured limit.

 

 

Output FDev=<Value>

Frequency of the output current is above or below the range that

Freq Out of Range

is configured as acceptable.

 

 

Input Transformer Temperature

The temperature of the PDU transformer exceeded the normal

Too High

limit, if applicable.

 

 

Main Breaker Open

The Main Input Switch is Off.

Alarm Active

 

 

 

<User Contact Name>

A user-configured contact connected to the PDU monitoring unit

Alarm Active

is reporting an alarm condition.

 

 

No UPS Input

The Q1 circuit breaker is open, and the PDU is not receiving

Breaker Q1 Open

power from the UPS.

 

 

Branch Ckt Pos: <nn>

Current on one of the poles of branch circuit breaker nn exceeded

Current Over Limit

the configured limit.

 

 

Branch Ckt Pos: <nn>

Current on one of the poles of branch circuit breaker nn dropped

Current Under Limit

below the configured limit.

 

 

Fan Rotation Failure

There is a failure in one of the fans. The fan needs to be replaced,

Alarm Active

if applicable.

 

 

24

60 kW InfraStruXure PDU — Operation and Configuration

Image 32
Contents 60kW InfraStruXure PDU Page How to find updates to this manual About This ManualAudience Companion manualsPage Contents Operation Specifications Product Information Safety Safety symbols used in this manualCross-reference symbols used in this manual OverviewInput Voltage Circuit Breaker Sizing Installation/MaintenanceReceiving/moving Total power off procedure Emergency Power Off EPOEMI Front view OverviewInfraStruXure PDU Front view interior Rear view of PDU with transformer interior PDURear view of PDU without transformer interior PDU monitoring unit User connection plate Multi-Branch Cordset Adapters SKU #Compatible APC 208V PDUs PDU Display Interface       Navigating through screens Top-level status screensTop-level menu screen Password-protected screens Power Factor Load-Meter ScreenVolt-Meter Screen Contacts Screen OverviewInput Contacts Open or ClosedAlarm Relay Map Relay output. For example, AlarmHow to connect contacts to the PDU monitoring unit Breakers Screen Main InputAlarms Screen New Logged ItemsEntire Log Clear LogGlobal Alarm ConfigLoading Limits Voltage LimitsPDU Alarms Alarm Condition ExplanationBranch Ckt Limits Panel ScreenBranch Ckt Loading Top right distribution panel Panel ConfigurationCircuit breakers occupying positions 08, 10, and 12 on Global Panel Config Config Screen System PasswordSystem/Network Date/TimeElectrical Config Input ConfigOutput Config Manufacturer DataFactory Defaults Firmware UpdatesHow to Apply Power to the System OperationFor PDUs with and without a transformer How to Ensure Total Power Off For PDU with transformer Open turnPage Communication Configuration InfraStruXure PDU Management OptionsInfraStruXure Manager Network management interfacesConfiguring the InfraStruXure Manager Connect the InfraStruXure PDU to the InfraStruXure ManagerConnect the InfraStruXure PDU to your network Configuring the Network Management InterfaceConfiguration Overview TCP/IP configuration methods Device IP Configuration WizardBootp & Dhcp configuration Option 43 = 01 04 31 41 50 43 where Remote access to the control console Local access to the control consoleUse apc for the User Name and Password Choose Network from the Control Console menu Use apc for both User Name and PasswordControl console Quick-Start manual for access information Web interfaceSnmp FTP and SCP KW InfraStruXure PDU-Operation and Configuration Important Safety Instructions Customizing and Updating the PDUCircuit Breakers Power CablesPDU Orderable Part List Customizing and Updating the PDU Add a circuit breaker on the PDU How to Add Circuit Breakers and Power CablesAdd a power cable to the PDU Customizing and Updating the PDU ATS 0 ATS 1 ATS Atsen How to connect contacts to the PDU monitoring unit How to Test the EPO Switch To test your EPO wiring and switchesSafety warnings Customizing and Updating the PDU From a local computer How to Download Firmware UpgradesUpgrading the PDU monitor processor Xmodem Specifications 60kW InfraStruXure PDUCompliance InfraStruXure Standard Warranty Product InformationProduct Information APC Three-Phase Systems Life-Support PolicyHow to Obtain Service How to contact APCChanges by page number Appendix Changes in This ManualGeneral changes Page Index 60kW InfraStruXure PDU-Operation and Configuration Page Page Page APC Worldwide Customer Support