Electrical Installation: Relay Board (Optional)
Relay | Name | Events that will trigger the alarm | Mode | Comment | |
ID | |||||
|
|
|
| ||
|
|
|
|
| |
K11 | Bypass operation | • UPS is running in normal operation/ | Active on | Opr. mode | |
|
| bypass operation according to AS400/ |
|
| |
|
| Novell. |
|
| |
|
|
|
|
| |
K12 | Maintenance bypass ON | • The maintenance bypass switch is active. | Active on | Opr. mode | |
|
|
|
|
| |
K13 | • UPS is in | Active on | Opr. mode | ||
|
|
|
|
| |
K14 | Boost charge operation | • UPS is boost charging the batteries. | Active on | Opr. mode | |
|
|
|
|
| |
K15 | Fan fault | • Blocked or faulty fan. | Fail safe | Fault | |
|
|
|
|
| |
K16 | High equipment | • Static Switch temperature is high; | Fail safe | Warning | |
| temperature or inverter | • Main Inverter failure (high temperature |
|
| |
| fuse blown | or blown fuse); |
|
| |
|
| • Delta Inverter temperature is high; |
|
| |
|
| • Magnetics temperature is high; |
|
| |
|
| • Isolation Transformer temperature is high |
|
| |
|
| (optional); |
|
| |
|
| • Battery temperature is high. |
|
| |
|
|
|
|
| |
IN1 | Generator active | • System on generator |
| System is | |
|
|
|
| running on | |
|
|
|
| generator. | |
|
|
|
| Battery | |
|
|
|
| charging is | |
|
|
|
| derated. | |
|
|
|
|
| |
IN2 | Battery room ventilation | • Battery room ventilation |
| Ventilation | |
| fault |
|
| fault in | |
|
|
|
| battery | |
|
|
|
| room. | |
|
|
|
| Battery | |
|
|
|
| charging is | |
|
|
|
| off. | |
|
|
|
|
| |
IN3 - | Reserved for future use |
|
|
| |
IN8 |
|
|
|
| |
|
|
|
|
|
Symmetra MW 1000 kW 480 V Installation - | 25 |