American Power Conversion MW manual AC Output, AC Input External Bypass SSW, Heat Dissipation

Page 35

 

 

Specifications: Electrical Specification

AC Output

 

 

 

AC Output

 

 

 

 

 

 

 

Voltage

480 V

 

Current Nom

1203 A

 

Max (note 11)

1504 A

 

Recommended cable (per phase)

5 × 500 kcmil

 

 

 

 

AC Input External Bypass SSW

The External Bypass SSW is designed to accommodate a continuous overload of 25%.

AC Input External Bypass SSW

External Bypass SSW Max Input Current (100% load)

1203 A

 

 

Heat Dissipation

105.5 kBTU/hr (note 10)

Notes

1.Nominal (Nom): Input current based on rated load.

2.Maximum (Max): Input current based on full battery recharge + nominal input voltage + rated load.

3.Current limitation (A) through electronic current limiting is based on full battery recharge + nominal load and -15% input voltage (see “Required Breaker Settings” ).

4.Input, Output and Battery1 and Battery2 circuit cables shall be run in separate conduits or raceways. Cables shall be rated at 600 V as a minimum.

5.Nominal battery voltage at 2.0 volts/cell.

6.Recommendation: All cables shall be sized in accordance with 2002 NEC 210-19 FPN No. 4 branch feeder voltage drop of 3%. Voltage drop not considered in above chart. Application- specific Input Cable Ampacity may vary from above chart.

7.Equipment Grounding Conductors shall be sized in accordance with Table 250-122 of the 2002 NEC and shall be installed in accordance with Article 250 Section VI and Section VII of the 2002 NEC. Grounding Electrode Conductors shall be sized in accordance with Article 250.66 and Table 250.66 of the 2002 NEC and should be installed in accordance with Article 250

Symmetra MW 1000 kW 480 V Installation - 990-4112E

31

Image 35
Contents Installation Page Contents Specifications Symbols used in this guide SafetyEPO Installation safetyControl Section UPS SectionsSerial number Inverter SectionConfiguration 1 Inverter Section placed to the left ConfigurationsTotal width of UPS sections 4138 mm/163 Weight Configuration 2 Inverter Section placed to the rightExternal Bypass Static Switch Power wiring overview Typical UPS Wiring PrincipleInput/Output wiring precautions External disconnection switchesTop Cable Entry Preparing for top cable entry defaultBattery cable connections top cable entry Front view of Input/Output Section Ground and AC cable connections top cable entry Preparing for bottom cable entry Bottom Cable EntryElectrical Installation Bottom Cable Entry Battery cable connections bottom cable entry Battery BAT 1 + BAT 2 + IN/OUT power cable bottom entry Ground and AC cable connections bottom cable entry Bypass Static Switch Wiring Top cable entry Bottom cable entry Connectionplane 0P0957 Communication cable overviewLocation of optional Relay Board Relay Board OptionalCommunication cables with optional Relay Board Relay Board functions Relay Name Events that will trigger the alarm Mode CommentIN1 Page High-impedance grounding Low-Impedance/High-Impedance GroundingLow-impedance grounding Specifications Low-Impedance/High-Impedance Grounding Installation Planning Data Electrical SpecificationDC Input AC InputHeat Dissipation AC OutputAC Input External Bypass SSW 16 National Electrical Code Size Temperature Rating of Cables See Table Recommended cable, bolt, and lug sizes Torque specificationsOutput and downstream breakers minimum settings Required Breaker SettingsInput and upstream breakers minimum settings Dual Utility Installation Nema General Specifications 480990-4112E