Page 23

 

Electrical Installation: Bypass Static Switch Wiring

Top cable entry

 

 

 

 

 

 

 

 

 

Top view of top cable entry

 

 

Top view of AC IN & OUT cable

 

 

 

connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1 IN

L1 OUT

L2 IN

L2 OUT

L3 IN

L3 OUT

PE

 

 

 

 

 

 

 

 

UPS Summary

 

 

Port for communication cables

 

 

 

~

~

 

L1 IN

L2 IN

L3 IN

 

 

 

L1 OUT

L2 OUT

L3 OUT

 

 

 

 

 

 

1.75 in /

1.75 in /

44.45 mm

44.45 mm

 

 

2.3 in / 58 mm

Loosen the 8 bolts to remove top cover.

No drilling or cutting should take place over the top of the UPS.

Note

Drill holes for conduits. Re-fit the covers. Install the conduits.

Feed cables through conduits. Connect cables at cable connection points as illustrated.

Connect grounding electrode conductor to busbar locations as shown.

Symmetra MW 1000 kW 480 V Installation - 990-4112E

19

Image 23
Contents Installation Page Contents Specifications Symbols used in this guide SafetyEPO Installation safetyControl Section UPS SectionsSerial number Inverter SectionConfiguration 1 Inverter Section placed to the left ConfigurationsTotal width of UPS sections 4138 mm/163 Weight Configuration 2 Inverter Section placed to the rightExternal Bypass Static Switch Power wiring overview Typical UPS Wiring PrincipleInput/Output wiring precautions External disconnection switchesTop Cable Entry Preparing for top cable entry defaultBattery cable connections top cable entry Front view of Input/Output Section Ground and AC cable connections top cable entry Preparing for bottom cable entry Bottom Cable EntryElectrical Installation Bottom Cable Entry Battery cable connections bottom cable entry Battery BAT 1 + BAT 2 + IN/OUT power cable bottom entry Ground and AC cable connections bottom cable entry Bypass Static Switch Wiring Top cable entry Bottom cable entry Connectionplane 0P0957 Communication cable overviewLocation of optional Relay Board Relay Board OptionalCommunication cables with optional Relay Board Relay Board functions Relay Name Events that will trigger the alarm Mode CommentIN1 Page High-impedance grounding Low-Impedance/High-Impedance GroundingLow-impedance grounding Specifications Low-Impedance/High-Impedance Grounding Installation Planning Data Electrical SpecificationDC Input AC InputHeat Dissipation AC OutputAC Input External Bypass SSW 16 National Electrical Code Size Temperature Rating of Cables See Table Recommended cable, bolt, and lug sizes Torque specificationsOutput and downstream breakers minimum settings Required Breaker SettingsInput and upstream breakers minimum settings Dual Utility Installation Nema General Specifications 480990-4112E