Electrical Installation: Relay Board (Optional)
Relay Board functions
The Relay Board informs the user of the operation mode, status, and alarm conditionsand has 8 ports on the input side and 16 output terminals.
Use Normally Closed (NC) contacts for Fail safe Mode and Normally Open (NO) for Active on.
Note
Relay | Name | Events that will trigger the alarm | Mode | Comment | |
ID  | |||||
  | 
  | 
  | 
  | ||
  | 
  | 
  | 
  | 
  | |
K1  | Common Alarm  | • Any of the functions below, except relays  | Fail safe  | Warning  | |
  | 
  | K8, K9, K10, K11;  | 
  | 
  | |
  | 
  | • Inverter section fault;  | 
  | 
  | |
  | 
  | • Main PSU fault;  | 
  | 
  | |
  | 
  | • System locked in operation mode;  | 
  | 
  | |
  | 
  | • Internal memory fault;  | 
  | 
  | |
  | 
  | • Internal communication fault.  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |
K2  | Battery voltage out of  | • DC voltage is too high (shut down);  | Fail safe  | Warning  | |
  | tolerance  | • DC voltage is under warning level;  | 
  | 
  | |
  | 
  | • DC voltage is low (shut down).  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |
K3  | Mains out of tolerance  | • Mains voltage RMS value is out of  | Fail safe  | Warning  | |
  | 
  | tolerance;  | 
  | 
  | |
  | 
  | • Mains waveform not accepted (fast  | 
  | 
  | |
  | 
  | detector);  | 
  | 
  | |
  | 
  | • Mains frequency is out of tolerance.  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |
K4  | Bypass out of tolerance  | • Bypass voltage RMS value is out of  | Fail safe  | Warning  | |
  | 
  | tolerance;  | 
  | 
  | |
  | 
  | • Bypass waveform not accepted (fast  | 
  | 
  | |
  | 
  | detector);  | 
  | 
  | |
  | 
  | • Bypass frequency is out of tolerance.  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |
K5  | Battery condition fault  | • Battery monitor has detected a weak  | Fail safe  | Fault  | |
  | 
  | battery;  | 
  | 
  | |
  | 
  | • Battery monitor has detected a defective  | 
  | 
  | |
  | 
  | battery.  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |
K6  | Battery disconnected  | • Battery breaker tripped/open.  | Fail safe  | Fault  | |
  | 
  | 
  | 
  | 
  | |
K7  | System overload  | • Output load exceeded 100%;  | Fail safe  | Fault  | |
  | 
  | • Delta Inverter current limiter is active;  | 
  | 
  | |
  | 
  | • Main Inverter current limiter is active.  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |
K8  | Output out of tolerance  | • Output voltage RMS value is out of  | Fail safe  | Fault  | |
  | 
  | tolerance;  | 
  | 
  | |
  | 
  | • Output waveform not accepted (fast  | 
  | 
  | |
  | 
  | detector);  | 
  | 
  | |
  | 
  | • Output frequency is out of tolerance.  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | |
K9  | Normal operation  | • UPS is running in normal operation.  | Active on  | Opr. mode  | |
  | 
  | 
  | 
  | 
  | |
K10  | Battery operation  | • UPS is running in battery operation.  | Active on  | Opr. mode  | |
  | 
  | 
  | 
  | 
  | 
24  | Symmetra MW 1000 kW 480 V Installation -   |