American Power Conversion MW manual Relay Board functions

Page 28

Electrical Installation: Relay Board (Optional)

Relay Board functions

The Relay Board informs the user of the operation mode, status, and alarm conditionsand has 8 ports on the input side and 16 output terminals.

Use Normally Closed (NC) contacts for Fail safe Mode and Normally Open (NO) for Active on.

Note

Relay

Name

Events that will trigger the alarm

Mode

Comment

ID

 

 

 

 

 

 

 

 

 

K1

Common Alarm

• Any of the functions below, except relays

Fail safe

Warning

 

 

K8, K9, K10, K11;

 

 

 

 

• Inverter section fault;

 

 

 

 

• Main PSU fault;

 

 

 

 

• System locked in operation mode;

 

 

 

 

• Internal memory fault;

 

 

 

 

• Internal communication fault.

 

 

 

 

 

 

 

K2

Battery voltage out of

• DC voltage is too high (shut down);

Fail safe

Warning

 

tolerance

• DC voltage is under warning level;

 

 

 

 

• DC voltage is low (shut down).

 

 

 

 

 

 

 

K3

Mains out of tolerance

• Mains voltage RMS value is out of

Fail safe

Warning

 

 

tolerance;

 

 

 

 

• Mains waveform not accepted (fast

 

 

 

 

detector);

 

 

 

 

• Mains frequency is out of tolerance.

 

 

 

 

 

 

 

K4

Bypass out of tolerance

• Bypass voltage RMS value is out of

Fail safe

Warning

 

 

tolerance;

 

 

 

 

• Bypass waveform not accepted (fast

 

 

 

 

detector);

 

 

 

 

• Bypass frequency is out of tolerance.

 

 

 

 

 

 

 

K5

Battery condition fault

• Battery monitor has detected a weak

Fail safe

Fault

 

 

battery;

 

 

 

 

• Battery monitor has detected a defective

 

 

 

 

battery.

 

 

 

 

 

 

 

K6

Battery disconnected

• Battery breaker tripped/open.

Fail safe

Fault

 

 

 

 

 

K7

System overload

• Output load exceeded 100%;

Fail safe

Fault

 

 

• Delta Inverter current limiter is active;

 

 

 

 

• Main Inverter current limiter is active.

 

 

 

 

 

 

 

K8

Output out of tolerance

• Output voltage RMS value is out of

Fail safe

Fault

 

 

tolerance;

 

 

 

 

• Output waveform not accepted (fast

 

 

 

 

detector);

 

 

 

 

• Output frequency is out of tolerance.

 

 

 

 

 

 

 

K9

Normal operation

• UPS is running in normal operation.

Active on

Opr. mode

 

 

 

 

 

K10

Battery operation

• UPS is running in battery operation.

Active on

Opr. mode

 

 

 

 

 

24

Symmetra MW 1000 kW 480 V Installation - 990-4112E

Image 28
Contents Installation Page Contents Specifications Safety Symbols used in this guideInstallation safety EPOUPS Sections Serial numberInverter Section Control SectionConfigurations Configuration 1 Inverter Section placed to the leftConfiguration 2 Inverter Section placed to the right Total width of UPS sections 4138 mm/163 WeightExternal Bypass Static Switch Typical UPS Wiring Principle Power wiring overviewExternal disconnection switches Input/Output wiring precautionsPreparing for top cable entry default Top Cable EntryBattery cable connections top cable entry Front view of Input/Output Section Ground and AC cable connections top cable entry Bottom Cable Entry Preparing for bottom cable entryElectrical Installation Bottom Cable Entry Battery cable connections bottom cable entry Battery BAT 1 + BAT 2 + IN/OUT power cable bottom entry Ground and AC cable connections bottom cable entry Bypass Static Switch Wiring Top cable entry Bottom cable entry Communication cable overview Connectionplane 0P0957Relay Board Optional Location of optional Relay BoardCommunication cables with optional Relay Board Relay Name Events that will trigger the alarm Mode Comment Relay Board functionsIN1 Page Low-impedance grounding Low-Impedance/High-Impedance GroundingHigh-impedance grounding Specifications Low-Impedance/High-Impedance Grounding Electrical Specification Installation Planning DataAC Input DC InputAC Input External Bypass SSW AC OutputHeat Dissipation 16 National Electrical Code Size Temperature Rating of Cables See Table Torque specifications Recommended cable, bolt, and lug sizesInput and upstream breakers minimum settings Required Breaker SettingsOutput and downstream breakers minimum settings Dual Utility Installation General Specifications 480 Nema990-4112E