Required Breaker Settings

The Symmetra® MW is a fault-tolerant system capable of handling and surviving overloads and internal/external faults. The overload performances and fault clearings are possible when the system meets specified minimum requirements for breaker settings. The settings are specified in the tables below, but some of them can also be found in the Electrical Specification section. The settings are all minimum settings and may not result in a drop-out.

See separate guide on parallel operation for information on required breaker settings in parallel systems.

See also

Input and upstream breakers — minimum settings

Q1, Q5, and any upstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

 

 

 

 

< 0.005

18 kA

--

Internal fault clearing

 

 

 

 

1880*

130

Overload on-line

 

 

 

 

1245

100

On-line

 

 

 

 

1370

110

On-line + Max. Battery

 

 

 

Charge

 

 

 

 

 

* Only applicable to Q1

 

Output and downstream breakers — minimum settings

Q2, Q4, Q6, and any downstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

 

 

 

 

< 0.005

18 kA

--

Internal fault clearing.

 

 

 

 

60

2406*

200

Overload on-line

 

 

 

 

600

1504*

125

Overload on-line

 

 

 

 

1203

100

On-line

 

 

 

 

* Only applicable to Q2 and Q4

Symmetra MW 1000 kW 480 V Installation - 990-4112E

35

Image 39
Contents Installation Page Contents Specifications Symbols used in this guide SafetyEPO Installation safetyControl Section UPS SectionsSerial number Inverter SectionConfiguration 1 Inverter Section placed to the left ConfigurationsTotal width of UPS sections 4138 mm/163 Weight Configuration 2 Inverter Section placed to the rightExternal Bypass Static Switch Power wiring overview Typical UPS Wiring PrincipleInput/Output wiring precautions External disconnection switchesTop Cable Entry Preparing for top cable entry defaultBattery cable connections top cable entry Front view of Input/Output Section Ground and AC cable connections top cable entry Preparing for bottom cable entry Bottom Cable EntryElectrical Installation Bottom Cable Entry Battery cable connections bottom cable entry Battery BAT 1 + BAT 2 + IN/OUT power cable bottom entry Ground and AC cable connections bottom cable entry Bypass Static Switch Wiring Top cable entry Bottom cable entry Connectionplane 0P0957 Communication cable overviewLocation of optional Relay Board Relay Board OptionalCommunication cables with optional Relay Board Relay Board functions Relay Name Events that will trigger the alarm Mode CommentIN1 Page Low-Impedance/High-Impedance Grounding Low-impedance groundingHigh-impedance grounding Specifications Low-Impedance/High-Impedance Grounding Installation Planning Data Electrical SpecificationDC Input AC InputAC Output AC Input External Bypass SSWHeat Dissipation 16 National Electrical Code Size Temperature Rating of Cables See Table Recommended cable, bolt, and lug sizes Torque specificationsRequired Breaker Settings Input and upstream breakers minimum settingsOutput and downstream breakers minimum settings Dual Utility Installation Nema General Specifications 480990-4112E