Required Breaker Settings
The Symmetra® MW is a 
See separate guide on parallel operation for information on required breaker settings in parallel systems.
See also
Input and upstream breakers — minimum settings
Q1, Q5, and any upstream breaker
Duration [S]  | Current [A]  | Total load [%]  | Event/Operation  | 
  | 
  | 
  | 
  | 
< 0.005  | 18 kA  | Internal fault clearing  | |
  | 
  | 
  | 
  | 
∞  | 1880*  | 130  | Overload   | 
  | 
  | 
  | 
  | 
∞  | 1245  | 100  | |
  | 
  | 
  | 
  | 
∞  | 1370  | 110  | |
  | 
  | 
  | Charge  | 
  | 
  | 
  | 
  | 
  | * Only applicable to Q1  | 
  | |
Output and downstream breakers — minimum settings
Q2, Q4, Q6, and any downstream breaker
Duration [S]  | Current [A]  | Total load [%]  | Event/Operation  | 
  | 
  | 
  | 
  | 
< 0.005  | 18 kA  | Internal fault clearing.  | |
  | 
  | 
  | 
  | 
60  | 2406*  | 200  | Overload   | 
  | 
  | 
  | 
  | 
600  | 1504*  | 125  | Overload   | 
  | 
  | 
  | 
  | 
∞  | 1203  | 100  | |
  | 
  | 
  | 
  | 
* Only applicable to Q2 and Q4
Symmetra MW 1000 kW 480 V Installation -   | 35  |