American Power Conversion MW manual Size Temperature Rating of Cables See Table

Page 37

Specifications: Electrical Specification

Size

 

Temperature Rating of Cables (See Table 310-13)

 

Size

 

 

 

 

 

 

 

 

 

60oC

75oC

90oC

60oC

75oC

90oC

 

 

(140oF)

(167oF)

(194oF)

(140oF)

(167oF)

(194oF)

 

 

 

Types

Types

 

 

Types

 

 

 

TBS,SA,SIS,FEP,

 

Types

TBS,SA,SIS,TH

 

 

 

FEPW,RH,RH

FEPB,MI,RHH,

 

HN,THHW,TH

 

AWG or

 

 

RH,RHW,TH

AWG or

Types

W,THHW,

RHW-2,THHN,

Types

W-2,THWN-2,

kcmil

HW,THW,

kcmil

TW,UF

THW,THWN,

THHW,THW-2,

TW,UF

RHH,RHW-2,

 

THWN,

 

 

 

XHHW,

THWN-2,USE-2,

 

USE-2,XHH,

 

 

 

 

XHHW,USE

 

 

 

USE,ZW

XHH,XHHW,XH

 

XHHW,

 

 

 

 

 

 

 

 

 

HW-2,ZW-2

 

 

XHHW-2,ZW-2

 

 

 

 

 

 

 

 

 

 

 

Copper

 

Aluminium or Copper-Clad Aluminium

 

 

 

 

 

 

 

 

 

18

-

-

14

-

-

-

-

16

-

-

18

-

-

-

-

14*

20

20

25

-

-

-

-

12*

25

25

30

20

20

25

12*

10*

30

35

40

25

30

35

10*

8

40

50

55

30

40

45

8

 

 

 

 

 

 

 

 

6

55

65

75

40

50

60

6

4

70

85

95

55

65

75

4

3

85

100

110

65

75

85

3

2

95

115

130

75

90

100

2

1

110

130

150

85

100

115

1

 

 

 

 

 

 

 

 

1/0

125

150

170

100

120

135

1/0

2/0

145

175

195

115

135

150

2/0

3/0

165

200

225

130

155

175

3/0

4/0

195

230

260

150

180

205

4/0

 

 

 

 

 

 

 

 

250

215

255

290

170

205

230

250

300

240

285

320

190

230

255

300

350

260

310

350

210

250

280

350

400

280

335

380

225

270

305

400

500

320

380

430

260

310

350

500

 

 

 

 

 

 

 

 

600

355

420

475

285

340

385

600

700

285

460

520

310

375

420

700

750

400

475

535

320

385

435

750

800

410

490

555

330

395

450

800

900

435

520

585

355

425

480

900

 

 

 

 

 

 

 

 

1000

455

545

615

375

445

500

1000

1250

495

590

665

405

485

545

1250

1500

520

625

705

435

520

585

1500

1750

545

650

735

455

545

615

1750

2000

560

665

750

470

560

630

2000

 

 

 

 

 

 

 

 

 

 

 

CORRECTION

FACTORS

 

 

 

 

 

 

Ambient

For ambient temperatures other than 30oC (86oF), multiply the allowable Ampacities shown above by

Ambient

Temp. (oC)

 

 

the appropriate factor shown below

 

Temp. (oF)

21-25

1.08

1.05

1.04

1.08

1.05

1.04

70-77

26-30

1.00

1.00

1.00

1.00

1.00

1.00

78-86

31-35

0.91

0.94

0.96

0.91

0.94

0.96

87-95

36-40

0.82

0.88

0.91

0.82

0.88

0.91

96-104

41-45

0.71

0.82

0.87

0.71

0.82

0.87

105-113

46-50

0.58

0.75

0.82

0.58

0.75

0.82

114-122

51-55

0.41

0.67

0.76

0.41

0.67

0.76

123-131

56-60

-

0.58

0.71

-

0.58

0.71

132-140

61-70

-

0.33

0.58

-

0.33

0.58

141-158

71-80

-

-

0.41

-

-

0.41

159-176

 

 

 

 

 

 

 

 

Reprinted with permission from NFPA 70-2005, National Electrical Code®, Copyright © 2004, National Fire Protection Association, Quincy, MA 02169. This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.

Symmetra MW 1000 kW 480 V Installation - 990-4112E

33

Image 37
Contents Installation Page Contents Specifications Symbols used in this guide SafetyEPO Installation safetySerial number UPS SectionsInverter Section Control SectionConfiguration 1 Inverter Section placed to the left ConfigurationsTotal width of UPS sections 4138 mm/163 Weight Configuration 2 Inverter Section placed to the rightExternal Bypass Static Switch Power wiring overview Typical UPS Wiring PrincipleInput/Output wiring precautions External disconnection switchesTop Cable Entry Preparing for top cable entry defaultBattery cable connections top cable entry Front view of Input/Output Section Ground and AC cable connections top cable entry Preparing for bottom cable entry Bottom Cable EntryElectrical Installation Bottom Cable Entry Battery cable connections bottom cable entry Battery BAT 1 + BAT 2 + IN/OUT power cable bottom entry Ground and AC cable connections bottom cable entry Bypass Static Switch Wiring Top cable entry Bottom cable entry Connectionplane 0P0957 Communication cable overviewLocation of optional Relay Board Relay Board OptionalCommunication cables with optional Relay Board Relay Board functions Relay Name Events that will trigger the alarm Mode CommentIN1 Page Low-impedance grounding Low-Impedance/High-Impedance GroundingHigh-impedance grounding Specifications Low-Impedance/High-Impedance Grounding Installation Planning Data Electrical SpecificationDC Input AC InputAC Input External Bypass SSW AC OutputHeat Dissipation 16 National Electrical Code Size Temperature Rating of Cables See Table Recommended cable, bolt, and lug sizes Torque specificationsInput and upstream breakers minimum settings Required Breaker SettingsOutput and downstream breakers minimum settings Dual Utility Installation Nema General Specifications 480990-4112E