Specifications: Required Breaker Settings
18 kA is the maximum peak
This is also applicable to the upstream breakers, and a control of the instantaneous trip setting in this part of the installation is required. The maximum peak
Note
Note
Note
The instantaneous trip setting must not be derated even though the UPS system is derated in system output power. The system size has no influence on the instantaneous trip setting.
For derated systems, the APC Application Team provides the correct breaker settings and breaker frame sizes.
For upstream breakers not mentioned in the table, the APC Application Team provides the correct breaker settings for
The following diagram shows a dual utility system in which the upstream breakers are named Q. Correct settings of upstream breaker settings are mandatory. The system can also be configured as a single utility system.
Dual Utility Installation
T1
Q
T2
Q
Q5
Q1
Q3 |
|
Q6 |
|
Q2 | Q4 |
36 | Symmetra MW 1000 kW 480 V Installation - |