Key Concepts continued

Configuring To configure PowerChute plus for simple signaling. Use PowerChute plus either one of these procedures. Note that steps 4 – 8 are com-

for simple

mon to both procedures.

signaling

1

(Re)install PowerChute plus. When the installation

 

 

program prompts for the UPS Type, select “Back-

 

 

UPS” and continue with the installation, including

 

 

a reboot of the system.

 

2

Run PowerChute plus and connect to the UPS.

 

3

Verify that the status line on the PowerChute plus

 

 

screen shows “On Line.” Proceed with step 4.

 

 

OR

 

1

With PowerChute plus running, select Communi-

 

 

cation Parameters from the Configuration

 

 

menu.

 

2

Click Simple Signalling. Click OK.

 

3

Close PowerChute plus.

 

4

If the UPS had previously been connected using

 

 

smart signaling:

 

 

a Unplug the UPS.

 

 

b Turn off the UPS output by pressing the Off

 

 

button for at least 5 seconds.

 

 

c Change communication cables, using the sim-

 

 

ple signaling cable from the interface kit. (See

 

 

“Choosing simple signaling cables: Table 1” on

 

 

page 4.)

 

5

Restart PowerChute plus and attach the server to

 

 

the UPS.

 

6

Verify that the status of the UPS on the

 

 

PowerChute plus screen shows “On Line.”

 

7

Simulate a utility power failure.

 

8

Confirm that the On Batt LED of Share-UPS is on,

 

 

indicating that Share-UPS is sending an On Bat-

 

 

tery signal to the server. See “LEDs: Table 2” on

 

 

page 8.

Continued on next page

12

Image 18
Contents Share-UPS Thank You Contents Setting Up Share-UPS Using the Share-UPS Menus Product Information Introduction Can delay shutdown of the UPS until all servers have Following list shows some of the features of ShareSupports advanced or simple signaling on its UPS and Share-UPS. See Using the Share-UPSOn next Cable supplied with your APC UPS Product Description On page 10. For Basic port specifications, see Basic port Tery and Low Battery conditions in the UPS. For furtherInformation see Simple versus smart signaling Table Pin assignments, onProduct Description If the LED Is… Then Share-UPS… Labeled… Product Description Simple Signaling Smart Signaling Key ConceptsCommunication Types Key Concepts If the UPS had previously been connected using Smart signalingUPS on page 23, when it may force a Low Battery signal Low Battery condition at the UPS. Share-UPS generates aTo the configured shutdown mode see Configuring Share An On Battery signal, causing the servers to shut downKey Concepts Installing Multiple Accessories Accessory slot with the higher number Accessory Priority PositionInterface Expander Share-UPS unit and the master server, you can purchase an AP9604. For installation instructions, refer to the userIf you need additional SmartSlot capacity between APC Expansion Chassis AP9600 or Triple ChassisInstalling Share-UPS Mounting Share-UPS NetShelter Figure Mounting Share-UPS on a wall Figure If using Optional Power input see Optional Connecting Share-UPSConfiguring Share-UPS, on If daisy-chaining multiple Share-UPS unitsAn Expansion Chassis, is already using Ate cable. See Choosing simple signalingIf an accessory, such as Measure-UPS II or Share-UPS use simple signaling for moniConfiguring Share-UPS Behavior Confirmed shutdown mode Effect Shutdown delay, go to ConfigurationEvent Down delay for a time longer than Share-UPS timerSetting. Otherwise, if the power returns after Actions and select UPS On Battery from the EventIf you want to change Share-UPS settings Com If configuring multiple Share-UPS units repeatTroubleshooting on Steps in the order given. If Share-UPS fails this test, seeUsing the Share-UPS Menus Using the Management PortPassword-protected menu interface allows you to view Using a dumb terminal or a computer and terminal emulaTion software, you can access the UPS remotely. Load, battery conditions, and current UPS statusAs possible. See Share-UPS Settings Nected, after three unsuccessful passwordFor security, change the password as soon Characters long, and is case-sensitiveMain Menu Main menu The following figure shows the Main menu. FigureMain menu only if Share-UPS has detected an APC Measure-UPS environmental monitoring accessoryUPS accessory For a description of the Measure-UPS Status screenFollowing table describes the items that appear on Main menuDescription Behavior UPS Status Display Connected UPS, output and load readings, battery informaAccess the UPS Status display, type s from the Main menu Following figure shows the UPS Status displayUPS Status Display Definitions Waiting to Power Load Status display, type c from the Main menu Tions on demand through Share-UPS. To access the UPSUPS Control Menu Following figure shows the UPS Control menuUPS Control menu It is connected to the UPSFollowing figure shows the Share-UPS Settings menu Share-UPS Settings MenuShare-UPS Settings menu allows you to configure Menu, type d from the Main menuShare-UPS Settings menu Definitions Paging Setup Menu Site IDspaceevent codeDuring a utility power outage when Share-UPS is config Following figure shows a typical sequence of eventsUred for paging That you may include in your dial string see Share-UPS Following figure shows the Paging Setup menuFollowing table lists some common modem commands Information, see the documentation supplied withPaging Setup menu Setting DescriptionPaging Setup Menu Definitions Warranty Information Exclusion of implied warranties therefore, the aforesaid Claims by third parties, or otherwise. This warranty givesPurpose. Some jurisdictions do not permit limitation or Specifically, APC is not liable for any costs, such as lostTroubleshooting Trouble Shooting Trouble Shooting Table Persists, follow this procedure For problems not covered in the troubleshooting chart seeTroubleshooting on page 26, or if the problem Material authorization RMA numberLife-Support Policy Specifications Assignments Specifications Normally Open Data bits with 1 start bit, 1 stop bit, and no parity Communications port. The port is configured as data termiManagement port is a standard 9-pin RS-232 serial Management port pin assignments are listed in the folFollowing table shows the product specifications for SpecificationShare-UPS Product Specifications Symbols IndexIndex Re-Boot All Servers Y, Z Page W. a p c c . c o m