American Power Conversion AP9207 manual Installing Multiple Accessories

Page 21

Chapter 2 Setting Up Share-UPS

Installing Multiple Accessories

Introduction

If your UPS configuration uses more than one APC acces-

 

sory, you must install them in the correct order for them to

 

work together properly. Connect the Share-UPS unit to the

 

Computer Interface port of the UPS, installing only a Mea-

 

sure-UPS II device in a SmartSlot accessory slot of the UPS.

 

Install all accessories according to priority, referring to “Pri-

 

ority of APC accessories: Table 4,” on page 16.

 

Note: SmartSlot accessories fit into APC UPSs and acces-

 

sories equipped with a SmartSlot accessory slot.

 

External accessories connect to the Computer Inter-

 

face port of the UPS or to the Advanced port of other

 

APC accessories (including Share-UPS).

 

 

Multiple

If you need more than the eight ports available with

Share-UPS units

Share-UPS, you can daisy-chain up to 5 Share-UPS units

 

together, provided that the total number of accessories

 

(including Share-UPS units and APC’s PowerView™) does

 

not exceed 10.

 

Note: When daisy-chaining Share-UPS units, you may need

 

to use a power adapter (see “Optional Power input,”

 

on page 9). You may also need to lengthen the timeout

 

delay in PowerChute plus by editing the [ ups ] sec-

 

tion of pwrchute.ini to include “TimeoutFactor = 100”

 

(or greater) to keep the software from interrupting the

 

daisy chain’s communications.

 

Each added Share-UPS unit provides seven more Basic

 

ports. Only one Advanced port in the daisy chain is avail-

 

able for connection to the master server. For connection

 

instructions, see step 2 of “Connection procedure” on page

 

21.

 

 

 

Continued on next page

15

Image 21
Contents Share-UPS Thank You Contents Setting Up Share-UPS Using the Share-UPS Menus Product Information Introduction Supports advanced or simple signaling on its Following list shows some of the features of ShareCan delay shutdown of the UPS until all servers have UPS and Share-UPS. See Using the Share-UPSOn next Cable supplied with your APC UPS Product Description Information see Simple versus smart signaling Table Tery and Low Battery conditions in the UPS. For furtherOn page 10. For Basic port specifications, see Basic port Pin assignments, onProduct Description If the LED Is… Then Share-UPS… Labeled… Product Description Simple Signaling Smart Signaling Key ConceptsCommunication Types Key Concepts Smart signaling If the UPS had previously been connected usingTo the configured shutdown mode see Configuring Share Low Battery condition at the UPS. Share-UPS generates aUPS on page 23, when it may force a Low Battery signal An On Battery signal, causing the servers to shut downKey Concepts Installing Multiple Accessories Accessory slot with the higher number Accessory Priority PositionInterface Expander If you need additional SmartSlot capacity between AP9604. For installation instructions, refer to the userShare-UPS unit and the master server, you can purchase an APC Expansion Chassis AP9600 or Triple ChassisInstalling Share-UPS Mounting Share-UPS NetShelter Figure Mounting Share-UPS on a wall Figure Configuring Share-UPS, on Connecting Share-UPSIf using Optional Power input see Optional If daisy-chaining multiple Share-UPS unitsIf an accessory, such as Measure-UPS II or Ate cable. See Choosing simple signalingAn Expansion Chassis, is already using Share-UPS use simple signaling for moniConfiguring Share-UPS Behavior Confirmed shutdown mode Effect Setting. Otherwise, if the power returns after Down delay for a time longer than Share-UPS timerShutdown delay, go to ConfigurationEvent Actions and select UPS On Battery from the EventIf configuring multiple Share-UPS units repeat If you want to change Share-UPS settings ComSteps in the order given. If Share-UPS fails this test, see Troubleshooting onUsing the Management Port Using the Share-UPS MenusTion software, you can access the UPS remotely. Using a dumb terminal or a computer and terminal emulaPassword-protected menu interface allows you to view Load, battery conditions, and current UPS statusFor security, change the password as soon Nected, after three unsuccessful passwordAs possible. See Share-UPS Settings Characters long, and is case-sensitiveMain menu The following figure shows the Main menu. Figure Main MenuUPS accessory Measure-UPS environmental monitoring accessoryMain menu only if Share-UPS has detected an APC For a description of the Measure-UPS Status screenFollowing table describes the items that appear on Main menuDescription Behavior Access the UPS Status display, type s from the Main menu Connected UPS, output and load readings, battery informaUPS Status Display Following figure shows the UPS Status displayUPS Status Display Definitions Waiting to Power Load UPS Control Menu Tions on demand through Share-UPS. To access the UPSStatus display, type c from the Main menu Following figure shows the UPS Control menuIt is connected to the UPS UPS Control menuShare-UPS Settings menu allows you to configure Share-UPS Settings MenuFollowing figure shows the Share-UPS Settings menu Menu, type d from the Main menuShare-UPS Settings menu Definitions Site IDspaceevent code Paging Setup MenuDuring a utility power outage when Share-UPS is config Following figure shows a typical sequence of eventsUred for paging Following table lists some common modem commands Following figure shows the Paging Setup menuThat you may include in your dial string see Share-UPS Information, see the documentation supplied withSetting Description Paging Setup menuPaging Setup Menu Definitions Warranty Information Purpose. Some jurisdictions do not permit limitation or Claims by third parties, or otherwise. This warranty givesExclusion of implied warranties therefore, the aforesaid Specifically, APC is not liable for any costs, such as lostTroubleshooting Trouble Shooting Trouble Shooting Table Troubleshooting on page 26, or if the problem For problems not covered in the troubleshooting chart seePersists, follow this procedure Material authorization RMA numberLife-Support Policy Specifications Assignments Specifications Normally Open Management port is a standard 9-pin RS-232 serial Communications port. The port is configured as data termiData bits with 1 start bit, 1 stop bit, and no parity Management port pin assignments are listed in the folFollowing table shows the product specifications for SpecificationShare-UPS Product Specifications Index SymbolsIndex Re-Boot All Servers Y, Z Page W. a p c c . c o m