American Power Conversion AP9207 manual UPS Status Display, Description

Page 41

UPS Status Display

Menu

The UPS Status display provides factory information on the

description

connected UPS, output and load readings, battery informa-

 

tion, and Measure-UPS accessory readings (if attached). To

 

access the UPS Status display, type s from the Main menu.

 

 

UPS Status

The following figure shows the UPS Status display.

display: Figure 6

-------------------------

MATRIX 5000 -----------------------

Utility Line:

213.1

VAC

Battery Info

UPS Output:

248.7

VAC

-----------------------

UPS Load:

013.0

%

Voltage:

55.62 VDC

Run Time:

0113 min

Capacity:

100.0 %

Load Power:

015.4

VA

Smart Cells:

002

Load Current:

04.26

A

Bad Cells:

000

UPS Temp:

024.3

C

Batt Date:

04/28/97

Freq:

60.00

Hz

Self Test:

NO

UPS ID:

UPS_IDEN

Manuf Date:

04/28/97

UPS S/N:

80033718

F/W Rev:

5ZI

Status: On-Line

>

UPS Status display definitions: Table 7

The following table describes the items that appear on the UPS Status display.

Item

Description

 

 

Utility Line

The input voltage from the utility, in volts AC.

 

 

UPS Output

The output voltage to the load from the UPS,

 

in volts AC.

 

 

UPS Load

The connected load (in watts) as a percentage

 

of the rated capacity of the UPS.

 

 

 

 

Continued on next page

35

Image 41
Contents Share-UPS Thank You Contents Setting Up Share-UPS Using the Share-UPS Menus Product Information Introduction Supports advanced or simple signaling on its Following list shows some of the features of ShareCan delay shutdown of the UPS until all servers have UPS and Share-UPS. See Using the Share-UPSOn next Cable supplied with your APC UPS Product Description Information see Simple versus smart signaling Table Tery and Low Battery conditions in the UPS. For furtherOn page 10. For Basic port specifications, see Basic port Pin assignments, onProduct Description If the LED Is… Then Share-UPS… Labeled… Product Description Communication Types Simple Signaling Smart SignalingKey Concepts Key Concepts Smart signaling If the UPS had previously been connected usingTo the configured shutdown mode see Configuring Share Low Battery condition at the UPS. Share-UPS generates aUPS on page 23, when it may force a Low Battery signal An On Battery signal, causing the servers to shut downKey Concepts Installing Multiple Accessories Interface Expander Accessory slot with the higher numberAccessory Priority Position If you need additional SmartSlot capacity between AP9604. For installation instructions, refer to the userShare-UPS unit and the master server, you can purchase an APC Expansion Chassis AP9600 or Triple ChassisInstalling Share-UPS Mounting Share-UPS NetShelter Figure Mounting Share-UPS on a wall Figure Configuring Share-UPS, on Connecting Share-UPSIf using Optional Power input see Optional If daisy-chaining multiple Share-UPS unitsIf an accessory, such as Measure-UPS II or Ate cable. See Choosing simple signalingAn Expansion Chassis, is already using Share-UPS use simple signaling for moniConfiguring Share-UPS Behavior Confirmed shutdown mode Effect Setting. Otherwise, if the power returns after Down delay for a time longer than Share-UPS timerShutdown delay, go to ConfigurationEvent Actions and select UPS On Battery from the EventIf configuring multiple Share-UPS units repeat If you want to change Share-UPS settings ComSteps in the order given. If Share-UPS fails this test, see Troubleshooting onUsing the Management Port Using the Share-UPS MenusTion software, you can access the UPS remotely. Using a dumb terminal or a computer and terminal emulaPassword-protected menu interface allows you to view Load, battery conditions, and current UPS statusFor security, change the password as soon Nected, after three unsuccessful passwordAs possible. See Share-UPS Settings Characters long, and is case-sensitiveMain menu The following figure shows the Main menu. Figure Main MenuUPS accessory Measure-UPS environmental monitoring accessoryMain menu only if Share-UPS has detected an APC For a description of the Measure-UPS Status screenDescription Behavior Following table describes the items that appear onMain menu Access the UPS Status display, type s from the Main menu Connected UPS, output and load readings, battery informaUPS Status Display Following figure shows the UPS Status displayUPS Status Display Definitions Waiting to Power Load UPS Control Menu Tions on demand through Share-UPS. To access the UPSStatus display, type c from the Main menu Following figure shows the UPS Control menuIt is connected to the UPS UPS Control menuShare-UPS Settings menu allows you to configure Share-UPS Settings MenuFollowing figure shows the Share-UPS Settings menu Menu, type d from the Main menuShare-UPS Settings menu Definitions Site IDspaceevent code Paging Setup MenuUred for paging During a utility power outage when Share-UPS is configFollowing figure shows a typical sequence of events Following table lists some common modem commands Following figure shows the Paging Setup menuThat you may include in your dial string see Share-UPS Information, see the documentation supplied withSetting Description Paging Setup menuPaging Setup Menu Definitions Warranty Information Purpose. Some jurisdictions do not permit limitation or Claims by third parties, or otherwise. This warranty givesExclusion of implied warranties therefore, the aforesaid Specifically, APC is not liable for any costs, such as lostTroubleshooting Trouble Shooting Trouble Shooting Table Troubleshooting on page 26, or if the problem For problems not covered in the troubleshooting chart seePersists, follow this procedure Material authorization RMA numberLife-Support Policy Specifications Assignments Specifications Normally Open Management port is a standard 9-pin RS-232 serial Communications port. The port is configured as data termiData bits with 1 start bit, 1 stop bit, and no parity Management port pin assignments are listed in the folShare-UPS Following table shows the product specifications forSpecification Product Specifications Index SymbolsIndex Re-Boot All Servers Y, Z Page W. a p c c . c o m