5.0 Operation

Audible alarm operation

The UPS’s audible alarm beeps four times every 30 seconds during on- battery operation. The alarm beeps continuously when low-battery condi- tions are reached. This is the default operation. You may configure the audible alarm operation such that response to utility failure is delayed by 30 seconds, silenced until low-battery conditions are reached, or muted during both on-battery and low-battery conditions.

Minimum battery capacity to restart

You may configure the UPS so that it will not restart upon restoration of the utility until the battery has been recharged to 90%, 25%, 10%, or 0% of capacity. This function helps eliminate short run times when repetitive utility failures occur. The default setting is 0%.

Shut down, turn off delay

You may set the UPS’s shutdown or turn-off delay interval to 20, 180, 300, or 600 seconds. The default setting is 20 seconds. Extension of the delay is useful when an operating system’s final shutdown routine is longer than 20 seconds.

Turn on delay

You may set the UPS’s turn-on delay to 0, 60, 180, or 300 seconds. The default setting is 0 seconds.

24

Image 26
Contents Smart-UPS Important safety instructions Radio frequency interferenceTable of Contents Specifications Storing the UPSIntroduction OverviewRemote interfaces Battery replacement indicators and testSmartBoost Extended capabilitiesSafety EnglishSécurité FrançaisSicherheit Vorsicht¡Seguridad ¡Atencion400VA UPS-rear panel Presentation400VA UPS-front panel Receiving inspection InstallationPlacement 100, 120 Vac versions 220/230/240 Vac versionCharge the batteries Auto-on operationTurn on accessories Plug in the accessory devicesConfigure Option Switch 4 and UPS Enable switch Plug in the master devicePlug loads into UPS Enable the UPSManual operation Operation Test button functions 5.2.1 Line Voltage bar graph Output Power bar graph UPS self-testLow battery Audible alarmsOn-battery alarm Replace batteryOption switches Option SwitchVac version No function not used Status reporting MonitoringPower management Operation customizing Shut down, turn off delay Audible alarm operationMinimum battery capacity to restart Turn on delayInterface Kits PowerChute SoftwareUPS Monitoring Computer Interface port Difficulty Difficulté Schwierigkeit Dificultad Possible cause TroubleshootingSolution Troubleshooting UPS Battery replacement check Obtaining service Extended storage Storing the UPSStorage conditions Output characteristics SpecificationsTransfer characteristics InputOperating Environment Battery and charger UPS version VacSurge and noise suppression Approvals WeightPhysical Size H´W´DTypical run times versus load Load Run Time Typical computer VA † minutes ‡ EquivalentsLimited Warranty Life support policy∗ Mailing