7.0Difficulty
7.1Troubleshooting
PROBLEM: | UPS will not turn on |
|
|
Possible cause: | No load or insufficient load at the Master outlet. |
Solution: | To turn on UPS and accessories, load must be larger |
| than 40 Watts and be turned on. |
|
|
Possible cause: | UPS Enable switch is in the off ( O ) position. |
Solution: | Turn on the rear panel UPS Enable switch. |
|
|
Possible cause: | UPS’s circuit breaker is tripped (button is extended). |
Solution: | Reduce the UPS’s load by unplugging equipment and |
| reset the circuit breaker (press button on rear panel). |
|
|
Possible cause: | Very low utility voltage or dead outlet. |
Solution: | Check outlet with a table lamp. If very dim, have |
| utility voltage checked by an electrician. |
|
|
PROBLEM: | UPS operates |
| voltage is thought to exist. |
|
|
Possible cause: | UPS’s circuit breaker is tripped (button is extended). |
Solution: | Unplug equipment to reduce the UPS’s load. Press the |
| button on the rear panel to reset circuit breaker. |
|
|
Possible cause: | Very high, low, or |
Solution: | Test the input voltage with UPS’s Line Voltage bar |
| graph (see Sec. 5.2.1). Inexpensive fuel powered |
| generators can cause distorted line |
| Option Switch 1 to the on (down) position. |
|
|
PROBLEM: | UPS “beeps” occasionally. |
|
|
Possible cause: | This is normal; the UPS is protecting your computer |
| equipment from momentary sags or swells. |
|
|
PROBLEM: | UPS beeps more than once or twice an hour. |
|
|
Possible cause: | Chronically high or distorted line voltage. |
Solution: | Set Option Switches 1 and 2 to match input voltage |
| range. Alternatively, set Option Switch 3 to the on |
| (down) position (see Secs. 5.4 and 5.5.4). |
|
|
31