APC 600 user manual Vac version No function not used, 220/230/240 Vac version

Page 22

5.0 Operation

5.5.2 Option Switch 2

Option Switch 2 functions differently for different versions of the UPS.

100 Vac version No function; not used.

120 Vac version

The UPS’s factory-set input voltage limits for on-line and SmartBoost operation are centered on the nominal input voltage of 120 Vac (see also Sec. 9.1). When Option Switch 2 is set to the on ( I ) position, the upper and lower transfer voltages are lowered by 4% and centered on a nominal input of 115 Vac. This is useful where nominal input voltage is 110 to 115 Vac.

220/230/240 Vac version

The UPS’s factory-set on-battery output voltage and input voltage limits for on-line and SmartBoost operation are designed for use in regions where the nominal line voltage is 220 to 230 Vac. When Option Switch 2 is set to the on ( I ) position, the upper and lower transfer voltages are raised by 4% and centered on a nominal input of 240 Vac. In addition, the on-battery output voltage is increased to 240 Vac.

5.5.3 Option Switch 3

When Option Switch 3 is set to the on ( I ) position, the UPS’s audible alarm is disabled for the first 30 seconds of on-battery operation. This function is useful where brief power interruptions are frequent and cause the alarm to become annoying.

5.5.4 Option Switch 4

When Option Switch 4 is set to the on ( I ) position, the UPS’s low-battery alarm interval is extended from 2 minutes (factory setting) to 5 minutes. This function is useful if the UPS is protecting a computer system that requires more than 2 minutes warning to perform a graceful shutdown.

20

Image 22
Contents Smart-UPS Important safety instructions Radio frequency interferenceTable of Contents Specifications Storing the UPSIntroduction OverviewRemote interfaces Battery replacement indicators and testSmartBoost Extended capabilitiesSafety EnglishSécurité FrançaisSicherheit Vorsicht¡Seguridad ¡AtencionPresentation 600VA UPS-100 and 120 Vac versions600VA UPS-220/230/240 Vac version Placement InstallationReceiving inspection 100, 120 Vac versions 220/230/240 Vac versionEnable UPS Plug loads into UPSSwitch on load equipment Switch on the UPSOperation Alarm disable button Power on buttonPower standby button Test buttonOutput Power bar graph Line Voltage bar graphLow battery Audible alarmsOn-battery alarm Replace batteryOption switches Option SwitchVac version No function not used Status reporting MonitoringPower management Operation customizing Shut down, turn off delay Audible alarm operationMinimum battery capacity to restart Turn on delayUPS Monitoring PowerChute SoftwareInterface Kits Computer interface port Difficulty Difficulté Schwierigkeit Dificultad Solution TroubleshootingPossible cause Troubleshooting Battery replacement check Obtaining service Storage conditions Storing the UPSExtended storage Output characteristics SpecificationsTransfer characteristics InputSurge and noise suppression Battery and charger UPS version VacOperating Environment Approvals WeightPhysical Size H´W´DTypical run times versus load Load Run Time Typical computer VA † Minutes ‡ EquivalentsPage Limited Warranty Life support policy∗ Mailing