APC 600 user manual Specifications, Input, Transfer characteristics, Output characteristics

Page 38

9.0 Specifications

9.1 Input

UPS version (Vac):

100

120

220/230/240

Nominal input voltage (Vac): single phase

 

100

 

120

230

 

 

 

 

 

 

 

Nominal input frequency:

 

 

 

50 or 60 Hz.

 

Internally selected by microprocessor.

 

 

 

 

 

 

 

 

 

 

 

 

Input protection:

 

 

8 Amp

 

7 Amp

5 Amp

Push-to-reset circuit breaker.

 

 

 

 

 

 

Input connections: IEC 320 male inlet coupler. 120 and 100 Vac versions

include 6 ft (2 m) line cord, with a NEMA 5-15P three pronged plug.

 

 

 

 

 

 

 

9.2 Transfer characteristics

 

 

 

 

 

 

 

 

 

Frequency limits for on-line operation:

 

50 or 60 Hz, ±5%

 

 

 

 

 

 

Lower input voltage, on-line operation:

 

80 Vac

 

90 Vac

173 Vac

Upper input voltage, on-line operation:

 

110 Vac

 

132 Vac

253 Vac

SmartBoost operation line voltage(Vac):

 

80–90

 

90–103

173–196

Transfer time:

 

 

 

2 ms typical;

(1 ms is 0.001 seconds).

 

 

4 ms maximum.

 

 

 

 

 

 

 

Note that these are the default values. Transfer parameters may be configured using UPS monitoring software.

9.3 Output characteristics

On-battery output voltage (Vac):

100 ±5%

115 ±5%

225 ±5%

 

 

 

 

Maximum output current:

6 Amp

5.2 Amp

2.7 Amp

 

 

 

 

Maximum load:

 

600 VA or

 

400 W at 0.67 power factor

 

 

 

 

On-battery Frequency:

50 or 60 Hz, ±0.1 Hz.

Synchronized to mains frequency during brownout.

 

 

 

 

 

 

On-battery waveshape:

 

sinewave.

 

Protection: Overcurrent and short-circuit protected, latching shutdown upon overload.

Output connections: 100 and 120 Vac versions have four NEMA 5-15R receptacles. 220/230/240 Vac version has four IEC 320 output couplers and includes two 6 ft (2 m) output cords with IEC 320 couplers and one IEC rewireable plug adapter.

36

Image 38
Contents Smart-UPS Important safety instructions Radio frequency interferenceTable of Contents Specifications Storing the UPSIntroduction OverviewRemote interfaces Battery replacement indicators and testSmartBoost Extended capabilitiesSafety EnglishSécurité FrançaisSicherheit Vorsicht¡Seguridad ¡AtencionPresentation 600VA UPS-100 and 120 Vac versions600VA UPS-220/230/240 Vac version Receiving inspection InstallationPlacement 100, 120 Vac versions 220/230/240 Vac versionEnable UPS Plug loads into UPSSwitch on load equipment Switch on the UPSOperation Alarm disable button Power on buttonPower standby button Test buttonOutput Power bar graph Line Voltage bar graphLow battery Audible alarmsOn-battery alarm Replace batteryOption switches Option SwitchVac version No function not used Status reporting MonitoringPower management Operation customizing Shut down, turn off delay Audible alarm operationMinimum battery capacity to restart Turn on delayInterface Kits PowerChute SoftwareUPS Monitoring Computer interface port Difficulty Difficulté Schwierigkeit Dificultad Possible cause TroubleshootingSolution Troubleshooting Battery replacement check Obtaining service Extended storage Storing the UPSStorage conditions Output characteristics SpecificationsTransfer characteristics InputOperating Environment Battery and charger UPS version VacSurge and noise suppression Approvals WeightPhysical Size H´W´DTypical run times versus load Load Run Time Typical computer VA † Minutes ‡ EquivalentsPage Limited Warranty Life support policy∗ Mailing