6.0 UPS Monitoring

6.4 Computer interface port

The computer i terface port is diagramed below. Those with technical abilities wishing to use this port in a special application should be aware of the following limitations and capabilities of the interface.

Outputs at Pins 3, 5, and 6 are open-collector outputs which must be pulled up to a common referenced supply no greater than +40 Vdc. The transistors are capable of a maximum noninductive load of 25 mAdc. Use only Pin 4 as the common.

The output at Pin 2 generates a low-to-high RS-232 level when the output load transfers to UPS battery power. The pin is normally at a low RS-232 level.

When on-battery, the UPS shuts down (after a delay) when a high RS-232 level is applied to Pin 1 for 4.5 seconds.

An unregulated +24 Vdc appears at Pin 8 of the interface port whenever the UPS is powered. The supply is limited to 40 mAdc maximum.

Applying a momentary (approx. 1 sec.) high RS-232 level to Pin 7 turns the UPS on. A momentary low RS-232 level turns the UPS off. Pin 7 should be normally unconnected.

26

Image 28
Contents Smart-UPS Important safety instructions Radio frequency interferenceTable of Contents Specifications Storing the UPSIntroduction OverviewBattery replacement indicators and test SmartBoostRemote interfaces Extended capabilitiesSafety EnglishSécurité FrançaisSicherheit Vorsicht¡Seguridad ¡AtencionPresentation 600VA UPS-100 and 120 Vac versions600VA UPS-220/230/240 Vac version Placement InstallationReceiving inspection 100, 120 Vac versions 220/230/240 Vac versionEnable UPS Plug loads into UPSSwitch on load equipment Switch on the UPSOperation Power on button Power standby buttonAlarm disable button Test buttonOutput Power bar graph Line Voltage bar graphAudible alarms On-battery alarmLow battery Replace batteryOption switches Option SwitchVac version No function not used Status reporting MonitoringPower management Operation customizing Audible alarm operation Minimum battery capacity to restartShut down, turn off delay Turn on delayUPS Monitoring PowerChute SoftwareInterface Kits Computer interface port Difficulty Difficulté Schwierigkeit Dificultad Solution TroubleshootingPossible cause Troubleshooting Battery replacement check Obtaining service Storage conditions Storing the UPSExtended storage Specifications Transfer characteristicsOutput characteristics InputSurge and noise suppression Battery and charger UPS version VacOperating Environment Weight PhysicalApprovals Size H´W´DTypical run times versus load Load Run Time Typical computer VA † Minutes ‡ EquivalentsPage Limited Warranty Life support policy∗ Mailing