AC International SV01B, V0100 operating instructions 2 I/O Setup Parameters

Page 19

Commissioning

4.5.2I/O Setup Parameters

Code

Possible Settings

IMPORTANT

No. Name

Default Selection

 

Assertion Level

2

1

Low

P120 and the Assertion Level switch

 

 

must both match the desired assertion

 

 

 

 

 

 

 

 

level unless P100, P121…P123 are

 

 

2

High

all set to 0. Otherwise an F.AL fault

 

 

will occur.

 

 

 

 

TB-13A Input

0 0

None

Disables input

Function

 

1

AUTO Reference: 0-10 VDC

For frequency mode, see P160...P161,

 

 

TB-13B Input

 

2

AUTO Reference: 4-20 mA

For PID mode, see P204…P205,

 

For vector torque mode, see P330

 

 

 

Function

 

3

AUTO Reference: Preset

For frequency mode see P131...P137,

 

 

TB-13C Input

 

 

 

For PID mode, see P231…P233,

 

 

 

For torque mode see, P331…P333

Function

 

 

 

 

4

AUTO Reference: MOP Up

• Normally open: Close input to

 

 

 

 

 

 

increase or decrease speed, PID

 

 

5

AUTO Reference: MOP Down

setpoint or torque setpoint.

 

 

 

 

• MOP Up is not active while in STOP

6AUTO Reference: Keypad

7AUTO Reference: Network

8

Control Select

Use when P100 = 4, 5 to switch

 

 

between terminal strip control and local

 

 

or remote keypad control.

9

Network Enable

Required to start the drive through the

 

 

network.

 

10

Reverse Rotation

Open = Forward

Closed = Reverse

11

Start Forward

See note for typical circuit

12

Start Reverse

 

 

13 Run Forward

See note for typical circuit

14 Run Reverse

 

 

15

Jog Forward

Jog Forward speed = P134

16

Jog Reverse

Jog Reverse speed = P135

 

 

Active even if P112 = 0

17

Accel/Decel #2

See P125, P126

 

18

DC Brake

See P174; close input to override P175

19

Auxiliary Ramp to Stop

Normally closed: Opening input will

 

 

ramp drive to STOP according to P127,

 

 

even if P111 is set to Coast (0 or 1).

20

Clear Fault

Close to reset fault

 

21

External Fault .

Normally closed circuit; open to trip

22

Inverse External Fault .

Normally open circuit; close to trip

WARNING!

Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be deactivated or a fault condition induced.

18

ENGLISH

Image 19
Contents Operating Instructions Contents Visible deficiencies / incompleteness immediately to your About these instructionsClaim Visible transport damage immediately to the forwarderElectrical connection Safety informationInstallation GeneralWarns of potential damage to material Icon Signal WordsOperation Warns of impending dangerStandards and application conditions Technical data120VAC Doubler / 240VAC Models Ratings240VAC Models Drive Derating Mains Output CurrentDimensions and mounting InstallationType Mains connection to 240VAC Single-Phase Supply Electrical installationPower Connections Mains connection to 120VAC Single-Phase SupplyESV…N06T… 3/PE AC Mains connection to Three-Phase SupplyMotor Connection Mains and Motor Terminations400V Fuses/cable cross-sectionsRecommendations Type 240V13A Control terminalsAssertion level of digital inputs Commissioning Local Mode P100 = 0, 4, this button will start the driveLocal Keypad & Display Drive Displays and Modes of Operation Parameter settingElectronic programming module EPM Code Possible Settings No. Name Default Selection Basic Setup ParametersParameter menu Acceleration Selection Drives except when using resetDefault setting is Motor Overload Minimum P103Upon a stop command, allowing Faults, or when power is appliedPrior to faulting or power loss Power-up2 I/O Setup Parameters Code Possible Settings Name Default Selection Network Control Active Standard Reference Active De-energizes when PID feedbackAttempts fail Active for start controlNetwork Activated Requires optional communication VDC Load VDC Torque VDC Power kWTB-14 Output Dynamic BrakingCode Advanced Setup ParametersDrive displays , and either CLim When the limit is reached,Display Depends on mode of operation See Section Slip 10.0Is installed Reset to 60 Hz default settings See NoteFault circuitry may be disabled! Check P100 and P121...P123 Displayed when P199 is set to 1 orPID Parameters Setpoint by more than the value Sleep DelayP242 or when the PID loop P200 = 0…2 Drive will start againVector Parameters If P300 = 2...5, motor calibration Calibration Enabled Must be programmed first An alternatingMotor Stator 4.00 Current Loop 9990Network Parameters Diagnostic ParametersKeypad Status Display Terminal and Protection Status DisplayStatus/Warning Messages Troubleshooting and DiagnosticsStatus / Warning Cause Remedy Format = Drive Configuration MessagesExample Stop Source DisplayFault Cause Remedy Fault MessagesIs set to 13 or Digital Input More than one digital input set forMOP function Up, Down Change PID setpoint referenceVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.