AC International SV01B Drive Configuration Messages, Example, Stop Source Display, Format =

Page 33

Troubleshooting and Diagnostics

 

Status / Warning

Cause

Remedy

 

 

 

 

 

PID Mode Active

Drive has been put into PID

 

 

 

Mode. See P200.

 

 

 

 

 

 

Sleep Mode is active

See P240...P242

 

 

 

 

 

 

Start Pending

The drive has tripped into a fault

To disable Auto-Restart, set

 

 

and will automatically restart

P110 = 0...2

 

 

(P110 = 3...6)

 

 

PID Mode disabled.

Drive has been taken out of PID

 

 

 

Mode. See P200.

 

 

 

 

 

 

Output frequency = 0 Hz

Stop has been commanded from

Apply Start command (Start

 

(outputs U, V, W inhibited)

the keypad, terminal strip, or

Control source depends on

 

 

network

P100)

5.2Drive Configuration Messages

When the Mode button is pressed and held, the drive’s display will provide a 4-digit code that indicates how the drive is configured. If the drive is in a Stop state when this is done, the display will also indicate which control source commanded the drive to Stop

(the two displays will alternate every second).

Configuration Display

Format = x.y.zz x = Control Source:

y = Mode:

zz = Reference:

= Local Keypad

= Speed mode

= Keypad s t

= Terminal Strip

= PID mode

= 0-10 VDC (TB-5)

= Remote Keypad

= Vector Torque mode

= 4-20 mA (TB-25)

= Network

 

= Jog

 

 

= Network

 

 

= MOP

 

 

= Preset 1...7

Example:

= Local Keypad Start control, Speed mode, Keypad speed reference

= Terminal Strip Start control, PID mode, 0-10 VDC setpoint reference

= Network Start control, Vector Torque mode, Preset Torque #2 reference

 

Stop Source Display

Format = x

= Stop command came from Local Keypad

 

= Stop command came from Terminal Strip

 

= Stop command came from Remote Keypad

 

= Stop command came from Network

32

ENGLISH

Image 33
Contents Operating Instructions Contents Claim About these instructionsVisible transport damage immediately to the forwarder Visible deficiencies / incompleteness immediately to yourInstallation Safety informationGeneral Electrical connectionOperation Icon Signal WordsWarns of impending danger Warns of potential damage to materialStandards and application conditions Technical dataRatings 120VAC Doubler / 240VAC Models240VAC Models Drive Derating Mains Output CurrentInstallation Dimensions and mountingType Power Connections Electrical installationMains connection to 120VAC Single-Phase Supply Mains connection to 240VAC Single-Phase SupplyMotor Connection Mains connection to Three-Phase SupplyMains and Motor Terminations ESV…N06T… 3/PE ACRecommendations Type Fuses/cable cross-sections240V 400VControl terminals 13AAssertion level of digital inputs Local Mode P100 = 0, 4, this button will start the drive CommissioningLocal Keypad & Display Parameter setting Drive Displays and Modes of OperationElectronic programming module EPM Basic Setup Parameters Code Possible Settings No. Name Default SelectionParameter menu Default setting is Motor Overload Selection Drives except when using resetMinimum P103 AccelerationPrior to faulting or power loss Faults, or when power is appliedPower-up Upon a stop command, allowing2 I/O Setup Parameters Code Possible Settings Name Default Selection Attempts fail De-energizes when PID feedbackActive for start control Network Control Active Standard Reference ActiveTB-14 Output VDC Load VDC Torque VDC Power kWDynamic Braking Network Activated Requires optional communicationCode Advanced Setup ParametersDisplay Depends on mode of operation See Section CLim When the limit is reached,Slip 10.0 Drive displays , and eitherFault circuitry may be disabled! Check P100 and P121...P123 Reset to 60 Hz default settings See NoteDisplayed when P199 is set to 1 or Is installedPID Parameters P242 or when the PID loop Sleep DelayP200 = 0…2 Drive will start again Setpoint by more than the valueVector Parameters Motor Stator 4.00 Calibration Enabled Must be programmed first An alternatingCurrent Loop 9990 If P300 = 2...5, motor calibrationNetwork Parameters Diagnostic ParametersKeypad Status Display Terminal and Protection Status DisplayTroubleshooting and Diagnostics Status/Warning MessagesStatus / Warning Cause Remedy Example Drive Configuration MessagesStop Source Display Format =Fault Cause Remedy Fault MessagesMOP function Up, Down Digital Input More than one digital input set forChange PID setpoint reference Is set to 13 orVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.