AC International V0100, SV01B Troubleshooting and Diagnostics, Status/Warning Messages

Page 32

Troubleshooting and Diagnostics

5Troubleshooting and Diagnostics

5.1Status/Warning Messages

 

Status / Warning

Cause

Remedy

 

 

 

 

 

DC-injection brake active

DC-injection brake activated

Deactivate DC-injection brake

 

 

• activation of digital input

• deactivate digital input

 

 

(P121...P123 = 18)

 

 

 

• automatically (P110 = 2, 4...6)

• automatically after P175 time

 

 

• automatically (P111 = 1, 3)

has expired

 

 

 

 

 

Drive ID warning

The Drive ID (P502) stored on

• Verify motor data

 

 

the EPM does not match the

(P302…P306) and perform

 

 

drive model.

Auto Calibration.

 

 

 

• Set drive mode (P300) to 0 or 1

 

 

 

• Reset the drive (P199 to 3 or 4)

 

 

 

and reprogram.

 

Motor Auto-calibration is being

See P300, P399

 

 

performed

 

 

 

 

 

 

 

An EPM that contains valid data

An attempt was made to change

Parameter settings can only be

 

from a previous software version

parameter settings

changed after the EPM data is

 

has been installed

 

converted to the current version

 

 

 

(P199 = 5)

 

 

 

 

 

Current Limit (P171) reached

Motor overload

• Increase P171

 

 

 

• Verify drive/motor are proper

 

 

 

size for application

 

 

 

 

 

Decel Override

The drive has stopped

If drive trips into fault:

 

 

decelerating to avoid tripping into

• Increase P105, P126

 

 

fault, due to excessive motor

• Install Dynamic Braking option

 

 

regen (2 sec max).

 

 

Error

Invalid data was entered, or an

 

 

 

invalid command was attempted

 

 

 

 

 

 

Fast Current Limit

Overload

Verify drive/motor are proper size

 

 

 

for application

 

 

 

 

 

Flying Restart Attempt after Fault

P110 = 5,6

 

 

 

 

 

 

OEM Settings Operation warning

An attempt was made to change

In OEM Settings mode, making

 

 

parameter settings while the

changes to parameters is not

 

 

drive is operating in OEM

permitted

 

 

Settings mode (P199 = 1)

 

 

 

 

 

 

OEM Defaults data warning

An attempt was made to use

Install an EPM containing valid

 

 

(or reset to) the OEM default

OEM Defaults data

 

 

settings (P199 = 1 or 2) using an

 

 

 

EPM without valid OEM data.

 

 

Fault Lockout

The drive attempted 5 restarts

• Drive requires manual reset

 

 

after a fault but all attempts were

• Check Fault History (P500)

 

 

unsuccessful (P110 = 3...6)

and correct fault condition

 

PID Deceleration Status

PID setpoint has finished

 

 

 

its ramp but the drive is still

 

 

 

decelerating to a stop.

 

 

 

 

 

 

 

ENGLISH

31

Image 32
Contents Operating Instructions Contents About these instructions ClaimVisible transport damage immediately to the forwarder Visible deficiencies / incompleteness immediately to yourSafety information InstallationGeneral Electrical connectionIcon Signal Words OperationWarns of impending danger Warns of potential damage to materialTechnical data Standards and application conditions240VAC Models Ratings120VAC Doubler / 240VAC Models Mains Output Current Drive DeratingType InstallationDimensions and mounting Electrical installation Power ConnectionsMains connection to 120VAC Single-Phase Supply Mains connection to 240VAC Single-Phase SupplyMains connection to Three-Phase Supply Motor ConnectionMains and Motor Terminations ESV…N06T… 3/PE ACFuses/cable cross-sections Recommendations Type240V 400VAssertion level of digital inputs Control terminals13A Local Keypad & Display Local Mode P100 = 0, 4, this button will start the driveCommissioning Electronic programming module EPM Parameter settingDrive Displays and Modes of Operation Parameter menu Basic Setup ParametersCode Possible Settings No. Name Default Selection Selection Drives except when using reset Default setting is Motor OverloadMinimum P103 AccelerationFaults, or when power is applied Prior to faulting or power lossPower-up Upon a stop command, allowing2 I/O Setup Parameters Code Possible Settings Name Default Selection De-energizes when PID feedback Attempts failActive for start control Network Control Active Standard Reference ActiveVDC Load VDC Torque VDC Power kW TB-14 OutputDynamic Braking Network Activated Requires optional communicationAdvanced Setup Parameters CodeCLim When the limit is reached, Display Depends on mode of operation See SectionSlip 10.0 Drive displays , and eitherReset to 60 Hz default settings See Note Fault circuitry may be disabled! Check P100 and P121...P123Displayed when P199 is set to 1 or Is installedPID Parameters Sleep Delay P242 or when the PID loopP200 = 0…2 Drive will start again Setpoint by more than the valueVector Parameters Calibration Enabled Must be programmed first An alternating Motor Stator 4.00Current Loop 9990 If P300 = 2...5, motor calibrationDiagnostic Parameters Network ParametersTerminal and Protection Status Display Keypad Status DisplayStatus / Warning Cause Remedy Troubleshooting and DiagnosticsStatus/Warning Messages Drive Configuration Messages ExampleStop Source Display Format =Fault Messages Fault Cause RemedyDigital Input More than one digital input set for MOP function Up, DownChange PID setpoint reference Is set to 13 orVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.