AC International SV01B Motor Stator 4.00, Current Loop 9990, If P300 = 2...5, motor calibration

Page 29

Commissioning

Code

 

Possible Settings

 

 

IMPORTANT

 

No.

Name

Default Selection

 

 

 

 

 

 

 

 

(1)

Motor Stator

0.00

0.00

{W}

4.00

• Will be automatically programmed by

 

Resistance

 

 

 

 

 

P399

 

 

(1)

Motor Stator

0.0

0.0

 

{mH}

2000

• Changing these settings can

 

Inductance

 

 

 

 

 

adversely affect performance.

 

 

 

 

 

 

Contact factory technical support

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prior to changing

 

 

 

Torque Limit

100

0

 

{%}

400

When P300 = 5, sets the maximum

 

 

 

 

 

 

 

output torque.

 

 

 

Preset Torque

100

0

 

{%}

400

TB-13A activated; P121 = 3 and

 

Setpoint #1

 

 

 

 

 

P300 = 5

 

 

 

Preset Torque

100

0

 

{%}

400

TB-13B activated; P122 = 3 and

 

Setpoint #2

 

 

 

 

 

P300 = 5

 

 

 

Preset Torque

100

0

 

{%}

400

TB-13C activated; P123 = 3 and

 

Setpoint #3

 

 

 

 

 

P300 = 5

 

 

(1)

Current Loop P

0.25

0.00

 

.0

 

 

 

 

Gain

 

 

 

 

 

Changing these settings can adversely

(1)

Current Loop I

65

12

 

{ms}

9990

 

affect performance. Contact factory

 

Gain

 

 

 

 

 

 

 

 

 

 

 

technical support prior to changing.

 

Speed Loop

0.0

0.0

 

{%}

20.0

(1)

 

 

 

 

 

Adjustment

 

 

 

 

 

 

 

 

 

Motor Auto-

0

0

Calibration Not Done

 

• If P300 = 2...5, motor calibration

 

calibration

 

 

 

 

 

must be performed, but motor data

 

 

 

1

Calibration Enabled

 

must be programmed first

 

 

 

 

• An alternating

/

will occur if:

 

 

 

 

 

 

 

- motor calibration is attempted with

 

 

 

2

Calibration Complete

 

P300 = 0 or 1

 

 

 

 

 

 

- motor calibration is attempted

 

 

 

 

 

 

 

before programming motor data

Note

To run the Auto Calibration:

-Set P302...P306 according to motor nameplate

-Set P399 = 1

-Make sure motor is cold (20° - 25° C)

-Apply a Start command

-Display will indicate for about 40 seconds

-Once the calibration is complete, the display will indicate ; apply another Start command to actually start the motor

-Parameter P399 will now be set to 2.

(1)Any changes to this parameter will not take effect until the drive is stopped

28

ENGLISH

Image 29
Contents Operating Instructions Contents Claim About these instructionsVisible transport damage immediately to the forwarder Visible deficiencies / incompleteness immediately to yourInstallation Safety informationGeneral Electrical connectionOperation Icon Signal WordsWarns of impending danger Warns of potential damage to materialStandards and application conditions Technical data240VAC Models Ratings120VAC Doubler / 240VAC Models Drive Derating Mains Output CurrentType InstallationDimensions and mounting Power Connections Electrical installationMains connection to 120VAC Single-Phase Supply Mains connection to 240VAC Single-Phase SupplyMotor Connection Mains connection to Three-Phase SupplyMains and Motor Terminations ESV…N06T… 3/PE ACRecommendations Type Fuses/cable cross-sections240V 400VAssertion level of digital inputs Control terminals13A Local Keypad & Display Local Mode P100 = 0, 4, this button will start the driveCommissioning Electronic programming module EPM Parameter settingDrive Displays and Modes of Operation Parameter menu Basic Setup ParametersCode Possible Settings No. Name Default Selection Default setting is Motor Overload Selection Drives except when using resetMinimum P103 AccelerationPrior to faulting or power loss Faults, or when power is appliedPower-up Upon a stop command, allowing2 I/O Setup Parameters Code Possible Settings Name Default Selection Attempts fail De-energizes when PID feedbackActive for start control Network Control Active Standard Reference ActiveTB-14 Output VDC Load VDC Torque VDC Power kWDynamic Braking Network Activated Requires optional communicationCode Advanced Setup ParametersDisplay Depends on mode of operation See Section CLim When the limit is reached,Slip 10.0 Drive displays , and eitherFault circuitry may be disabled! Check P100 and P121...P123 Reset to 60 Hz default settings See NoteDisplayed when P199 is set to 1 or Is installedPID Parameters P242 or when the PID loop Sleep DelayP200 = 0…2 Drive will start again Setpoint by more than the valueVector Parameters Motor Stator 4.00 Calibration Enabled Must be programmed first An alternatingCurrent Loop 9990 If P300 = 2...5, motor calibrationNetwork Parameters Diagnostic ParametersKeypad Status Display Terminal and Protection Status DisplayStatus / Warning Cause Remedy Troubleshooting and DiagnosticsStatus/Warning Messages Example Drive Configuration MessagesStop Source Display Format =Fault Cause Remedy Fault MessagesMOP function Up, Down Digital Input More than one digital input set forChange PID setpoint reference Is set to 13 orVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.