AC International V0100 Slip 10.0, CLim When the limit is reached, Drive displays , and either

Page 24

 

 

 

 

 

Commissioning

Code

 

Possible Settings

 

 

IMPORTANT

No.

Name

Default Selection

 

 

 

 

 

 

Slip

0.0

0.0

{%}

10.0

Increase P170 until the motor speed no

 

Compensation

 

 

 

 

longer changes between no load and

 

 

 

 

 

 

full load conditions.

(1)

Current Limit

200

30

{%}

CLim

• When the limit is reached, the

 

 

 

 

 

max

drive displays , and either the

 

 

 

 

 

 

 

 

 

 

 

 

acceleration time increases or the

 

 

 

 

 

 

output frequency decreases.

 

 

 

 

 

 

• Digital outputs can also indicate

 

 

 

 

 

 

when the limit is reached; see P140,

 

 

 

 

 

 

P142.

 

 

 

 

 

 

• Refer to section 2.2 for CLimmax

 

DC Brake

0.0

0.0

{%}

30.0

Setting is a percent of the nominal DC

 

Voltage

 

 

 

 

bus voltage.

 

DC Brake Time

0.0

0.0

{s}

999.9

 

 

 

 

Note

 

 

 

 

 

 

CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING

 

 

 

DC Brake voltage (P174) is applied for the time specified by P175 with the

 

 

 

following exceptions:

 

 

If P111=1, 3 and P175=999.9 the brake voltage will be applied continuously until a run or fault condition occurs.

If P110=2, 4…6 and P175=999.9, brake voltage will be applied for 15s

If P121…P123=18 and the corresponding TB-13 input is CLOSED, brake voltage will be applied until the TB-13 input is OPENED or a fault condition occurs.

Display

0.00

0.00

 

50.00

Allows frequency display to be

Frequency

 

 

 

 

 

scaled

Multiplier

 

 

 

 

P178 = 0.00: Scaling disabled

 

 

 

 

 

P178 > 0.00: Display = Actual

 

 

 

 

 

 

Frequency X P178

 

 

Example: If P178 = 29.17 and actual frequency = 60 Hz,

 

 

 

Drive displays 1750 (rpm)

 

Run Screen

0

0

{Parameter Number} 599

0 = Normal Run Screen, this display

Display

 

 

 

 

 

depends on mode of operation.

 

 

 

 

 

 

See Section 4.2.

 

 

 

 

 

• Other selections choose a diagnostic

 

 

 

 

 

 

parameter to display (P501…P599).

Skip frequency 1

0.0

0.0

{Hz}

500

Drive will not run in the defined skip

Skip frequency 2

0.0

0.0

{Hz}

500

 

range; used to skip over frequencies

 

that cause mechanical vibration

 

 

 

 

 

 

Skip frequency

0.0

0.0

{Hz}

10.0

P181 and P182 define the start of

bandwidth

 

 

 

 

 

the skip ranges

 

 

 

 

 

• P184 > 0 defines the bandwidth of

 

 

 

 

 

 

both ranges.

 

 

Note

 

 

 

 

 

Bandwidth (Hz) = fs

(Hz) + P184 (Hz)

fs = P181 or P182

 

 

Example: P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz

(1) Any changes to this parameter will not take effect until the drive is stopped

 

 

 

 

ENGLISH

 

23

Image 24
Contents Operating Instructions Contents About these instructions ClaimVisible transport damage immediately to the forwarder Visible deficiencies / incompleteness immediately to yourSafety information InstallationGeneral Electrical connectionIcon Signal Words OperationWarns of impending danger Warns of potential damage to materialTechnical data Standards and application conditionsRatings 120VAC Doubler / 240VAC Models240VAC Models Mains Output Current Drive DeratingInstallation Dimensions and mountingType Electrical installation Power ConnectionsMains connection to 120VAC Single-Phase Supply Mains connection to 240VAC Single-Phase SupplyMains connection to Three-Phase Supply Motor ConnectionMains and Motor Terminations ESV…N06T… 3/PE ACFuses/cable cross-sections Recommendations Type240V 400VControl terminals 13AAssertion level of digital inputs Local Mode P100 = 0, 4, this button will start the drive CommissioningLocal Keypad & Display Parameter setting Drive Displays and Modes of OperationElectronic programming module EPM Basic Setup Parameters Code Possible Settings No. Name Default SelectionParameter menu Selection Drives except when using reset Default setting is Motor OverloadMinimum P103 AccelerationFaults, or when power is applied Prior to faulting or power lossPower-up Upon a stop command, allowing2 I/O Setup Parameters Code Possible Settings Name Default Selection De-energizes when PID feedback Attempts failActive for start control Network Control Active Standard Reference ActiveVDC Load VDC Torque VDC Power kW TB-14 OutputDynamic Braking Network Activated Requires optional communicationAdvanced Setup Parameters CodeCLim When the limit is reached, Display Depends on mode of operation See SectionSlip 10.0 Drive displays , and eitherReset to 60 Hz default settings See Note Fault circuitry may be disabled! Check P100 and P121...P123Displayed when P199 is set to 1 or Is installedPID Parameters Sleep Delay P242 or when the PID loopP200 = 0…2 Drive will start again Setpoint by more than the valueVector Parameters Calibration Enabled Must be programmed first An alternating Motor Stator 4.00Current Loop 9990 If P300 = 2...5, motor calibrationDiagnostic Parameters Network ParametersTerminal and Protection Status Display Keypad Status DisplayTroubleshooting and Diagnostics Status/Warning MessagesStatus / Warning Cause Remedy Drive Configuration Messages ExampleStop Source Display Format =Fault Messages Fault Cause RemedyDigital Input More than one digital input set for MOP function Up, DownChange PID setpoint reference Is set to 13 orVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.