AC International V0100, SV01B Fuses/cable cross-sections, Recommendations Type, 240V, 400V

Page 12

Installation

3.2.2Fuses/cable cross-sections

Note

Observe local regulations.

Local codes may supersede these recommendations

 

 

 

Recommendations

 

 

 

 

 

 

 

 

 

 

Type

 

Miniature

Fuse (2) or

Input Power Wiring

 

Fuse

circuit

Breaker(3)

(L1, L2, L3, PE)

 

 

 

 

 

breaker(1)

(N. America)

 

 

 

 

 

 

 

[mm²]

[AWG]

120V

ESV251N01SXB

M10 A

C10 A

10 A

 

1.5

14

1~

ESV371N01SXB

M16 A

C16 A

15 A

 

2.5

14

(1/N/PE)

ESV751N01SXB

M25 A

C25 A

25 A

 

4

10

 

ESV251N01SXB, ESV251N02SXB,

M10 A

C10 A

10 A

 

1.5

14

 

ESV371N01SXB, ESV371N02YXB

 

 

 

 

 

 

 

 

240V

ESV751N01SXB, ESV751N02YXB

M16 A

C16 A

15 A

 

2.5

14

1~

ESV112N02YXB

M20 A

C20 A

20 A

 

2.5

12

(2/PE)

 

ESV152N02YXB

M25 A

C25 A

25 A

 

2.5

12

 

 

 

ESV222N02YXB

M32 A

C32A

32 A

 

4

10

 

ESV371N02YXB, ESV751N02YXB

M10 A

C10 A

10 A

 

1.5

14

 

ESV112N02YXB, ESV152N02YXB,

M12 A

C12 A

12 A

 

1.5

14

 

ESV112N02TXB, ESV152N02TXB

 

240V

 

 

 

 

 

 

ESV222N02YXB, ESV222N02TXB

M20 A

C20 A

20 A

 

2.5

12

3~

 

(3/PE)

ESV402N02TXB

M32 A

C32 A

32 A

 

4.0

10

 

ESV552N02TXB

M35 A

C35 A

35 A

 

6.0

8

 

ESV752N02TXB

M45 A

C45 A

45 A

 

10

8

 

ESV371N04TXB...ESV222N04TXB

M10 A

C10 A

10 A

 

1.5

14

400V

ESV552N04TXB

M16 A

C16 A

20 A

 

2.5

14

or 480V

 

ESV752N04TXB

M20 A

C20 A

20 A

 

2.5

14

3~(3/PE)

 

 

ESV402N04TXB

M25 A

C25 A

25 A

 

4.0

10

 

ESV751N06TXB...ESV222N06TXB

M10 A

C10 A

10 A

 

1.5

14

600V

ESV402N06TXB

M12 A

C12 A

12 A

 

1.5

14

3~(3/PE)

ESV552N06TXB

M16 A

C16 A

15 A

 

2.5

14

 

ESV752N06TXB

M20 A

C20 A

20 A

 

2.5

12

(1)Installations with high fault current due to large supply mains may require a type D circuit breaker.

(2)UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN or JJS or equivalent.

(3)Thermomagnetic type breakers preferred.

Observe the following when using Ground Fault Circuit Interrupters (GFCIs):

Installation of GFCI only between supplying mains and controller.

The GFCI can be activated by:

-capacitive leakage currents between the cable screens during operation (especially with long, screened motor cables)

-connecting several controllers to the mains at the same time

-RFI filters

ENGLISH

11

Image 12
Contents Operating Instructions Contents About these instructions ClaimVisible transport damage immediately to the forwarder Visible deficiencies / incompleteness immediately to yourSafety information InstallationGeneral Electrical connectionIcon Signal Words OperationWarns of impending danger Warns of potential damage to materialTechnical data Standards and application conditionsRatings 120VAC Doubler / 240VAC Models240VAC Models Mains Output Current Drive DeratingInstallation Dimensions and mountingType Electrical installation Power ConnectionsMains connection to 120VAC Single-Phase Supply Mains connection to 240VAC Single-Phase SupplyMains connection to Three-Phase Supply Motor ConnectionMains and Motor Terminations ESV…N06T… 3/PE ACFuses/cable cross-sections Recommendations Type240V 400VControl terminals 13AAssertion level of digital inputs Local Mode P100 = 0, 4, this button will start the drive CommissioningLocal Keypad & Display Parameter setting Drive Displays and Modes of OperationElectronic programming module EPM Basic Setup Parameters Code Possible Settings No. Name Default SelectionParameter menu Selection Drives except when using reset Default setting is Motor OverloadMinimum P103 AccelerationFaults, or when power is applied Prior to faulting or power lossPower-up Upon a stop command, allowing2 I/O Setup Parameters Code Possible Settings Name Default Selection De-energizes when PID feedback Attempts failActive for start control Network Control Active Standard Reference ActiveVDC Load VDC Torque VDC Power kW TB-14 OutputDynamic Braking Network Activated Requires optional communicationAdvanced Setup Parameters CodeCLim When the limit is reached, Display Depends on mode of operation See SectionSlip 10.0 Drive displays , and eitherReset to 60 Hz default settings See Note Fault circuitry may be disabled! Check P100 and P121...P123Displayed when P199 is set to 1 or Is installedPID Parameters Sleep Delay P242 or when the PID loopP200 = 0…2 Drive will start again Setpoint by more than the valueVector Parameters Calibration Enabled Must be programmed first An alternating Motor Stator 4.00Current Loop 9990 If P300 = 2...5, motor calibrationDiagnostic Parameters Network ParametersTerminal and Protection Status Display Keypad Status DisplayTroubleshooting and Diagnostics Status/Warning MessagesStatus / Warning Cause Remedy Drive Configuration Messages ExampleStop Source Display Format =Fault Messages Fault Cause RemedyDigital Input More than one digital input set for MOP function Up, DownChange PID setpoint reference Is set to 13 orVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.