AC International SV01B Attempts fail, Active for start control, De-energizes when PID feedback

Page 21

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default

Selection

 

 

 

 

 

 

 

 

Relay Output

0

0

None

Disables the output

 

TB-16, 17

 

1

Run

Energizes when the drive is running

 

 

 

 

 

 

2

Reverse

Energizes when reverse rotation is active

 

 

 

3

Fault

De-energizes when the drive trips, or

 

 

 

 

 

power is removed

 

 

 

4

Inverse Fault

Energizes when the drive trips

 

 

 

5

Fault Lockout

P110 = 3...6: De-energizes if all restart

 

 

 

 

 

attempts fail

 

 

 

6

At Speed

Energizes when output frequency =

 

 

 

 

 

commanded frequency

 

 

 

7

Above Preset Speed #6

Energizes when output freq. > P136

 

 

 

8

Current Limit

Energizes when motor current = P171

 

 

 

9

Follower Loss (4-20 mA)

Energizes when 4-20 mA signal falls

 

 

 

 

 

below 2 mA

 

 

 

10

Loss of Load

Energizes when motor load drops

 

 

 

 

 

below P145; see also P146

 

 

 

11

Local Keypad Control Active

 

 

 

 

 

 

 

 

 

 

12

Terminal Strip Control Active

Energizes when the selected source is

 

 

 

13

Remote Keypad Control Active

active for start control

 

 

 

14

Network Control Active

 

 

 

 

15

Standard Reference Active

Energizes when P101 reference is active

 

 

 

16

Auto Reference Active

Energizes when Auto Reference

 

 

 

 

 

is activated using TB-13 input; see

 

 

 

 

 

P121...P123

 

 

 

17

Sleep Mode Active

See P240...P242

 

 

 

18

PID Feedback < Min. Alarm

Energizes when PID feedback signal

 

 

 

 

 

< P214

 

 

 

19

Inverse PID Feedback < Min.

De-energizes when PID feedback

 

 

 

 

Alarm

signal < P214

 

 

 

20

PID Feedback > Max Alarm

Energizes when PID feedback

 

 

 

 

 

signal > P215

 

 

 

21

Inverse PID Feedback > Max

De-energizes when PID feedback

 

 

 

 

Alarm

signal > P215

 

 

 

22

PID Feedback within

Energizes when PID feedback signal

 

 

 

 

Min/Max Alarm range

is within the Min/Max Alarm range; see

 

 

 

 

 

P214, P215

 

 

 

23

PID Feedback outside

Energizes when PID feedback signal is

 

 

 

 

Min/Max Alarm range

outside the Min/Max Alarm range; see

 

 

 

 

 

P214, P215

 

 

 

24

Reserved

 

 

 

 

 

 

 

 

 

 

25

Network Activated

Requires optional communication

 

 

 

 

 

module (refer to the network module

 

 

 

 

 

documentation).

 

 

 

 

 

 

20

 

 

 

ENGLISH

 

Image 21
Contents Operating Instructions Contents Claim About these instructionsVisible transport damage immediately to the forwarder Visible deficiencies / incompleteness immediately to yourInstallation Safety informationGeneral Electrical connectionOperation Icon Signal WordsWarns of impending danger Warns of potential damage to materialStandards and application conditions Technical dataRatings 120VAC Doubler / 240VAC Models240VAC Models Drive Derating Mains Output CurrentInstallation Dimensions and mountingType Power Connections Electrical installationMains connection to 120VAC Single-Phase Supply Mains connection to 240VAC Single-Phase SupplyMotor Connection Mains connection to Three-Phase SupplyMains and Motor Terminations ESV…N06T… 3/PE ACRecommendations Type Fuses/cable cross-sections240V 400VControl terminals 13AAssertion level of digital inputs Local Mode P100 = 0, 4, this button will start the drive CommissioningLocal Keypad & Display Parameter setting Drive Displays and Modes of OperationElectronic programming module EPM Basic Setup Parameters Code Possible Settings No. Name Default SelectionParameter menu Default setting is Motor Overload Selection Drives except when using resetMinimum P103 AccelerationPrior to faulting or power loss Faults, or when power is appliedPower-up Upon a stop command, allowing2 I/O Setup Parameters Code Possible Settings Name Default Selection Attempts fail De-energizes when PID feedbackActive for start control Network Control Active Standard Reference ActiveTB-14 Output VDC Load VDC Torque VDC Power kWDynamic Braking Network Activated Requires optional communicationCode Advanced Setup ParametersDisplay Depends on mode of operation See Section CLim When the limit is reached,Slip 10.0 Drive displays , and eitherFault circuitry may be disabled! Check P100 and P121...P123 Reset to 60 Hz default settings See NoteDisplayed when P199 is set to 1 or Is installedPID Parameters P242 or when the PID loop Sleep DelayP200 = 0…2 Drive will start again Setpoint by more than the valueVector Parameters Motor Stator 4.00 Calibration Enabled Must be programmed first An alternatingCurrent Loop 9990 If P300 = 2...5, motor calibrationNetwork Parameters Diagnostic ParametersKeypad Status Display Terminal and Protection Status DisplayTroubleshooting and Diagnostics Status/Warning MessagesStatus / Warning Cause Remedy Example Drive Configuration MessagesStop Source Display Format =Fault Cause Remedy Fault MessagesMOP function Up, Down Digital Input More than one digital input set forChange PID setpoint reference Is set to 13 orVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.