AC International V0100, SV01B operating instructions Vector Parameters

Page 28

Commissioning

4.5.5Vector Parameters

Code

 

Possible Settings

IMPORTANT

No.

Name

Default Selection

 

(1)

Drive Mode

0

0

Constant V/Hz

Constant torque V/Hz control for

 

 

 

 

 

general applications

 

 

 

1

Variable V/Hz

Variable torque V/Hz control for

 

 

 

 

 

centrifugal pump and fan applications

 

 

 

2

Enhanced Constant V/Hz

For single or multiple motor

 

 

 

3

Enhanced Variable V/Hz

applications that require better

 

 

 

performance than settings 0 or 1, but

 

 

 

 

 

 

 

 

 

 

cannot use Vector mode, due to:

 

 

 

 

 

• Missing required motor data

 

 

 

 

 

• Vector mode causing unstable motor

 

 

 

 

 

operation

 

 

 

4

Vector Speed

For single-motor applications requiring

 

 

 

 

 

higher starting torque and speed

 

 

 

 

 

regulation

 

 

 

5

Vector Torque

For single-motor applications requiring

 

 

 

 

 

torque control independent of speed

 

 

 

Note

 

 

 

 

To configure the drive for either Vector mode or Enhanced V/Hz mode:

P300 = 4, 5:

-Set P302...P306 according to motor nameplate

-Set P399 = 1

-Make sure motor is cold (20° - 25° C) and apply a Start command

-Display will indicate for about 40 seconds

-Once the calibration is complete, the display will indicate ; apply another Start command to actually start the motor

-If an attempt is made to start the drive in Vector or Enhanced V/Hz mode before performing the Motor Calibration, the drive will display and will not operate

P300 = 2, 3: Same as above but only need to set P302…P304

(1)

Motor Rated

 

0

{V}

600

 

 

Voltage

 

 

 

 

• Default setting = drive rating

(1)

Motor Rated

 

0.0

{A}

500.0

• Set to motor nameplate data

 

Current

 

 

 

 

 

(1)

Motor Rated

60

0

{Hz}

1000

 

 

Frequency

 

 

 

 

 

(1)

Motor Rated

1750

300

{RPM}

65000 Set to motor nameplate data

 

Speed

 

 

 

 

 

(1)

Motor Cosine Phi

0.80

0.40

 

0.99

 

 

 

 

Note

 

 

 

 

 

 

If motor cosine phi is not known, use one of the following formulas:

 

 

 

cos phi = motor Watts / (motor efficiency X P302 X P303 X 1.732)

 

 

 

cos phi = cos [ sin 1 (magnetizing current / motor current) ]

(1) Any changes to this parameter will not take effect until the drive is stopped

ENGLISH

27

Image 28
Contents Operating Instructions Contents About these instructions ClaimVisible transport damage immediately to the forwarder Visible deficiencies / incompleteness immediately to yourSafety information InstallationGeneral Electrical connectionIcon Signal Words OperationWarns of impending danger Warns of potential damage to materialTechnical data Standards and application conditions120VAC Doubler / 240VAC Models Ratings240VAC Models Mains Output Current Drive DeratingDimensions and mounting InstallationType Electrical installation Power ConnectionsMains connection to 120VAC Single-Phase Supply Mains connection to 240VAC Single-Phase SupplyMains connection to Three-Phase Supply Motor ConnectionMains and Motor Terminations ESV…N06T… 3/PE ACFuses/cable cross-sections Recommendations Type240V 400V13A Control terminalsAssertion level of digital inputs Commissioning Local Mode P100 = 0, 4, this button will start the driveLocal Keypad & Display Drive Displays and Modes of Operation Parameter settingElectronic programming module EPM Code Possible Settings No. Name Default Selection Basic Setup ParametersParameter menu Selection Drives except when using reset Default setting is Motor OverloadMinimum P103 AccelerationFaults, or when power is applied Prior to faulting or power lossPower-up Upon a stop command, allowing2 I/O Setup Parameters Code Possible Settings Name Default Selection De-energizes when PID feedback Attempts failActive for start control Network Control Active Standard Reference ActiveVDC Load VDC Torque VDC Power kW TB-14 OutputDynamic Braking Network Activated Requires optional communicationAdvanced Setup Parameters CodeCLim When the limit is reached, Display Depends on mode of operation See SectionSlip 10.0 Drive displays , and eitherReset to 60 Hz default settings See Note Fault circuitry may be disabled! Check P100 and P121...P123Displayed when P199 is set to 1 or Is installedPID Parameters Sleep Delay P242 or when the PID loopP200 = 0…2 Drive will start again Setpoint by more than the valueVector Parameters Calibration Enabled Must be programmed first An alternating Motor Stator 4.00Current Loop 9990 If P300 = 2...5, motor calibrationDiagnostic Parameters Network ParametersTerminal and Protection Status Display Keypad Status DisplayStatus/Warning Messages Troubleshooting and DiagnosticsStatus / Warning Cause Remedy Drive Configuration Messages ExampleStop Source Display Format =Fault Messages Fault Cause RemedyDigital Input More than one digital input set for MOP function Up, DownChange PID setpoint reference Is set to 13 orVerify drive and motor are proper Page SV01B

V0100, SV01B specifications

The AC International SV01B and V0100 represent a significant advancement in the realm of audio technology, specifically tailored for audiophiles and professionals seeking high-fidelity sound reproduction. These models have garnered attention for their impeccable engineering and innovative features designed to enhance the listening experience.

One of the standout characteristics of the SV01B is its superior sound quality, achieved through high-resolution audio capabilities. This model supports various audio formats, ensuring that users can enjoy music in its purest form. The SV01B employs advanced digital signal processing (DSP) that optimizes audio performance, reducing distortion and maintaining clarity at high volumes. Coupled with a robust amplifier, the SV01B delivers deep bass and crystal-clear highs, making it suitable for listening to a range of genres from classical to modern electronic music.

The V0100, on the other hand, brings together cutting-edge wireless technology with exceptional sound. It incorporates Bluetooth 5.0, ensuring a stable and high-quality connection with compatible devices. This feature allows users to experience seamless streaming without the hassle of tangled wires. The V0100 also supports aptX and AAC codecs, enabling low-latency audio playback, which is particularly beneficial for video content and gaming. Additionally, its multi-device connection capability allows users to switch between devices effortlessly, enhancing convenience.

Both the SV01B and V0100 showcase elegant designs that blend practicality with aesthetics. The chassis of these models is crafted from high-grade materials, providing durability while minimizing resonance. Furthermore, they feature intuitive controls, making it easy to adjust settings or switch tracks without interrupting the listening flow.

Battery life is another significant advantage of the V0100, which offers an impressive runtime on a single charge, ensuring that users can enjoy extended listening sessions without frequent recharging. The LED indicators provide clear feedback on connectivity and battery status, enhancing user experience.

In conclusion, the AC International SV01B and V0100 are remarkable audio devices that combine outstanding sound quality, advanced technology, and user-friendly features. They cater to both casual listeners and dedicated audiophiles, making them an excellent choice for anyone looking to elevate their audio experience.