Toshiba G8000 Transporting, Do not expose the unit to vibration or shock exceeding 0.5G

Page 27

8 Transporting

warning

When transporting the UPS by crane, follow the SPECIFIED WORK PROCEDURE. The suspension wire angle should be less than 60°.

The UPS falling or overturning may cause crushing, trapping or other personal injuries.

DO NOT tilt the UPS more than 10° from upright position.

Tilting the UPS more than 10° may cause crushing, trapping or other personal injuries.

caution

DO NOT transport, move, store, or place the UPS on its side.

Excessive force applied from heavy components inside may damage the UPS.

Do NOT expose the unit to vibration or shock exceeding 0.5G.

Excessive vibration or shock may cause damage to the UPS.

DO NOT allow the UPS to suffer shock or impact when unpacking.

Tools used to remove packaging materials may cause damage to the

UPS.

DO NOT install the UPS where water may fall on it.

Water may cause electrical shock, personal injury or UPS failure.

DO NOT push or pull on the sides of the packaging.or the UPS to move it. Always use a crane, forklift, or pallet jack for transporting and positioning the UPS.

Pushing/pulling on the sides of the unit to move it may result in damage to the UPS. (See Figure 4.1 Exterior Handling label.)

The UPS may be packed in a crate for extra protection during transportation. Avoid impact or vibration against the UPS during transportation. DO NOT expose the UPS directly to water.

G8000 Series with Isolated Output Installation and Operation Manual

19

Image 27
Contents G8000 Series Page G8000 Series Qualified Personnel only Uninterruptible Power System UPS Toshiba International Corporation PurposeToshiba’s Customer Support Center Toshiba Customer Support CenterTable of Contents Terminal Blocks, Terminal Bus, and Power Cables 11.3 Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsDo not tilt the UPS more than 10 from upright position General MaintenanceKeep the area arround the UPS clean Transporting/UnpackingAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Follow the torque criteria for tightening screws Wiring/ConnectionPerform wiring and connections with correct polarity Connect only one 1 ground wire to the earth ground terminalFor 100 and 150 kVA GND 150kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions150kVA UPS Exterior Dimensions Inches Do not expose the unit to vibration or shock exceeding 0.5G Transporting8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation UPS Clearance UnpackingAnchor Bolts Breaker UPS WiringAC Input Bypass Input AC Output Battery Terminal Blocks, Terminal Bus, and Power CablesBlock Number Cable Size Tightening Torque 100 KVA 150 KVA Bottom Cable Knockout Plates 100 kVA External BreakersBe sure to ground the UPS as specified Grounding WireSignal Name Operation Control WiresConnection Between UPS, Battery Cabinet & Bypass Breaker Jumper Cable Between the Neutral Terminal & Ground BUS Grounding ConfigurationUPS Specifications General SpecificationMechanical Specification Rated Capacity 150kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD Indicators50% Normal DisplayAC-VO AC- I O 50% Volt Freq .0Hz32TIM AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz DC-V BATT-V BATT- I 0A09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesOperation Types Pre-operational CheckPerform the pre-operational check before operating the UPS Step Startup ProceduresAC Vo 208 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Batt FAULT1 warning goes away Troubleshooting Emergency Power Off EPOTypes of Errors 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesAC O/P UV Button functions LCD Scroll w/ faults or warningsDo not open the front and/or rear panels Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not attempt to modify or relocate the UPSPage Page Industrial Division