14.5Stop
The procedure to stop the UPS is shown in Steps
LED Key
![]()
- LED Off
![]()
- LED On
- LED Flash
BYPASS
AC - Vo 208 V
AC - Io 50%
PRESS ‘UPS’ SWITCH
STEP 1
Transfer to Bypass supply as described in Switch Power Supply.
AC INPUT
BATTERIES
BYPASS INPUT
CONVERTER
![]()
FLOAT CHARGE
![]()
EQUAL CHARGE
![]()
DISCHARGE
UPS
INVERTER
AC |
|
SWITCH | AC OUTPUT |
| |
BYPASS |
|
UPS LED is “OFF”. BYPASS LED is “ON”.
BYPASS
MOVE 72B TO ‘OFF’ POSITION
STEP 2
Turn off the DC Input Breaker (72B) on the external battery cabinet, and, press the G8000 “STOP” button for at least 0.5 seconds.
AC INPUT
BATTERIES
BYPASS INPUT
CONVERTER
![]()
FLOAT CHARGE
![]()
EQUAL CHARGE
![]()
DISCHARGE
INVERTER
UPS
AC |
|
SWITCH | AC OUTPUT |
| |
BYPASS |
|
BATTERIES LED is “OFF”.
INVERTER LED flashes then “OFF”.
FLOAT CHARGE LED and CONVERTER LED are “OFF”.
AC INPUT
BATTERIES
BYPASS INPUT
BYPASS
PRESS ‘RUN’ SWITCH
| UPS |
CONVERTER | INVERTER |
FLOAT CHARGE | AC |
EQUAL CHARGE | |
DISCHARGE | SWITCH |
BYPASS
STEP 3
Wait until procedure is completed.
AC OUTPUT