11.4Control Wires

The control wires terminal layouts at TB1 (terminal bus 1) are shown below in Table 11.4.

 

 

 

 

 

Table 11.4 EXTERNAL CONNECTIONS

No.

 

I/O

 

 

Signal Name

 

Operation

1

 

Output

 

 

Low Battery

 

Closed at Low Battery

2

 

Output

 

 

Backup Operation

 

Closed during Backup Operation

3

 

Output

 

 

Fault

 

Closed if Faults present

4

 

Output

 

 

Inverter Supply

 

Closed during Normal Operation

5

 

Output

 

 

Warning

 

Closed if Warnings present

6

 

Input

}

 

P24

 

 

7

 

Input

 

Remote Run

 

Close to run UPS

 

 

 

8

 

Input

}

 

P24

 

 

9

 

Input

 

Remote Stop

 

Close to stop UPS

 

 

 

10

 

Output

 

 

Bypass Supply

 

Close during Bypass Operation

11

 

Output

 

 

Output Signal Ground

 

(Ground for pin #1 – 5 & #10)

12

 

Input

}

 

P24

 

Battery’s

13

 

Input

 

Battery Overheat

 

Overheat B-contact

 

 

 

14

 

Output

}

 

 

 

Bypass Breaker

15

 

Output

 

52C Trip Signal

 

Shunt Trip Signal by EPO

 

 

 

16

 

Output

}

 

 

 

Battery Breaker shunt trip

17

 

Output

 

72B Trip Signal

 

by EPO or Battery shutdown

 

 

 

18

 

Output

}

 

 

 

Battery breaker’s

19

 

Output

 

72B Aux. Contact

 

Auxiliary A-contact

 

 

 

20

 

 

 

 

 

 

 

21

 

Output

}

 

External EPO

 

Ext EPO (Customer) N.O. Contacts

22

 

Output

 

External EPO

 

Ext EPO (Customer) N.O. Contacts

 

 

 

Note: All control wiring should be #18 AWG (0.823 mm2) or larger.

34

G8000 Series with Isolated Output Installation and Operation Manual

Image 42
Contents G8000 Series Page G8000 Series Qualified Personnel only Uninterruptible Power System UPS Toshiba Customer Support Center PurposeToshiba’s Customer Support Center Toshiba International CorporationTable of Contents Terminal Blocks, Terminal Bus, and Power Cables 11.3 Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelImportant Safety Instructions Factory Authorized PersonnelSafety Precautions DisclaimerTransporting/Unpacking General MaintenanceKeep the area arround the UPS clean Do not tilt the UPS more than 10 from upright positionDo not transport, move, store, or place the UPS on its side Avoid vibration or shock exceeding 0.5GInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not install the UPS where water may fall on it Do not block air ventsInstallation Precautions Environment standardPage Connect only one 1 ground wire to the earth ground terminal Wiring/ConnectionPerform wiring and connections with correct polarity Follow the torque criteria for tightening screwsFor 100 and 150 kVA GND 150kVA UPS Warning Labels Weight and Dimensions Model Unit Shipping150kVA UPS Exterior Dimensions Inches Transporting Do not expose the unit to vibration or shock exceeding 0.5GTransporting By Crane 8.5 show examples of acceptable and unacceptable operationsTransporting By Forklift Transporting UPS by ForkliftOperating Precautions Storage/Operating EnvironmentPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation Unpacking UPS ClearanceAnchor Bolts UPS Wiring BreakerTerminal Blocks, Terminal Bus, and Power Cables AC Input Bypass Input AC Output BatteryBlock Number Cable Size Tightening Torque 100 KVA 150 KVA External Breakers Bottom Cable Knockout Plates 100 kVAGrounding Wire Be sure to ground the UPS as specifiedControl Wires Signal Name OperationConnection Between UPS, Battery Cabinet & Bypass Breaker Grounding Configuration Jumper Cable Between the Neutral Terminal & Ground BUSUPS Specifications General SpecificationMechanical Specification Rated Capacity 150kVA Electrical Specification Do not open the front coverOperator Interface UPS may not respond if the button press is too shortKey-Switch and Buttons Graphic display Panel KEY-SWITCH/OPERATING Buttons13.2 LCD/LED Indicators Graphic display Panel LCD/LED INDICAtorsLCD Indicators Name DescriptionVolt Freq .0Hz Normal DisplayAC-VO AC- I O 50% 50%DC-V BATT-V BATT- I 0A AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz 32TIMFault Display 09-09-06LCD Scroll AbbreveationsEpo and Control Power supply operating switches Operating the UPSOperation Types Pre-operational CheckPerform the pre-operational check before operating the UPS Startup Procedures StepAC Vo 208 AC Io 50% Switch Power Supply UPS→Bypass Bypass LED is onStop Complete Shutdown DC-V 0 BATT-V 0 BATT-I 0 aChanging Between Float Charge and Equalize Charge Make sure that the Float Charge LED is onMake sure that the Batt FAULT1 warning goes away Troubleshooting Emergency Power Off EPOTypes of Errors Faults and Warnings Data Screen 09-09-06LCD Fault & Warning Displays Fault DisplayFault Messages Over HeatAC O/P UV LCD Scroll w/ faults or warnings Button functionsDo not attempt to modify or relocate the UPS Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not open the front and/or rear panelsPage Page Industrial Division