Toshiba G8000 operation manual Block Number Cable Size Tightening Torque 100 KVA 150 KVA

Page 39

table 11.1 Recommended crimp type compression lugs

Wire Size

Wire

Recommendation

Crimp tool Required

 

Strand

 

 

Burndy type Y35 or Y46

 

Class

Vendor

Cat. No.

Color Key

Die Index

1/0

B

Burndy

YA25

Pink

12 / 348

 

I

Ilsco

CRA-1/OL

Pink

12 / 348

 

B

Burndy

YA25-LB

Black

13

2/0

B

Burndy

YA26

Black

13

 

I

Ilsco

CRA-2/OL

Black

13

 

B

Burndy

YA27-LB

Orange

14 / 101

3/0

B

Burndy

YA-27

Orange

14 / 101

 

I

Ilsco

CRB-3/OL

Orange

14 / 101

 

B

Burndy

YA28-LB

Purple

15

4/0

B

Burndy

YA28

Purple

15

 

I

Ilsco

CRB-4/OL

Purple

15

 

B

Burndy

YA29-LB

Yellow

16

300 MCM

B

Burndy

YA30

White

17 / 298

 

I

Ilsco

CRA-30OL

White

17 / 298

 

B

Burndy

YA32-LB

Red

18 / 324

table 11.2 recommended cable size and tightening torque for 100 KVA and 150 KVA UPS

Block Number

Cable Size

Tightening Torque

 

100 KVA

150 KVA

 

1

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

2

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

3

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

4

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

5

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

6

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

7

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

8

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

9

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

10

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

*11

Two AWG 3/0 or larger

Two 300 MCM or larger

275 in-lbs. (3.2 kg-m)

*12

Two AWG 3/0 or larger

Two 300 MCM or larger

275 in-lbs. (3.2 kg-m)

13

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

NOTE: Maximum cable size is 350 MCM

*One battery string (SEE NOTE, PAGE 36, if using multiple battery strings

G8000 Series with Isolated Output Installation and Operation Manual

31

Image 39
Contents G8000 Series Page G8000 Series Qualified Personnel only Uninterruptible Power System UPS Toshiba International Corporation PurposeToshiba’s Customer Support Center Toshiba Customer Support CenterTable of Contents Terminal Blocks, Terminal Bus, and Power Cables 11.3 Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsDo not tilt the UPS more than 10 from upright position General MaintenanceKeep the area arround the UPS clean Transporting/UnpackingAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Follow the torque criteria for tightening screws Wiring/ConnectionPerform wiring and connections with correct polarity Connect only one 1 ground wire to the earth ground terminalFor 100 and 150 kVA GND 150kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions150kVA UPS Exterior Dimensions Inches Do not expose the unit to vibration or shock exceeding 0.5G Transporting8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation UPS Clearance UnpackingAnchor Bolts Breaker UPS WiringAC Input Bypass Input AC Output Battery Terminal Blocks, Terminal Bus, and Power CablesBlock Number Cable Size Tightening Torque 100 KVA 150 KVA Bottom Cable Knockout Plates 100 kVA External BreakersBe sure to ground the UPS as specified Grounding WireSignal Name Operation Control WiresConnection Between UPS, Battery Cabinet & Bypass Breaker Jumper Cable Between the Neutral Terminal & Ground BUS Grounding ConfigurationUPS Specifications General SpecificationMechanical Specification Rated Capacity 150kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD Indicators50% Normal DisplayAC-VO AC- I O 50% Volt Freq .0Hz32TIM AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz DC-V BATT-V BATT- I 0A09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesOperation Types Pre-operational CheckPerform the pre-operational check before operating the UPS Step Startup ProceduresAC Vo 208 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Batt FAULT1 warning goes away Troubleshooting Emergency Power Off EPOTypes of Errors 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesAC O/P UV Button functions LCD Scroll w/ faults or warningsDo not open the front and/or rear panels Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not attempt to modify or relocate the UPSPage Page Industrial Division