14.4Switch Power Supply (UPS→Bypass)
The procedure to transfer between the UPS supply and the bypass supply is shown in Steps
LED Key
![]()
- LED Off
![]()
- LED On
- LED Flash
STEP 1
Check AC INPUT LED and BYPASS LED are on to make sure power is being delivered to the UPS.
AC INPUT
BATTERIES
BYPASS INPUT
UPS SUPPLY
AC - Vo 208 v
AC - Io 50%
| UPS |
|
CONVERTER | INVERTER |
|
FLOAT CHARGE | AC |
|
EQUAL CHARGE |
| |
DISCHARGE | SWITCH | AC OUTPUT |
|
BYPASS
STEP 2
Press the “BYPASS” button for at least 0.5 seconds.
UPS LED is “OFF”.
BYPASS
BYPASS LED is “ON”.
AC INPUT
BATTERIES
BYPASS INPUT
CONVERTER
![]()
FLOAT CHARGE
![]()
EQUAL CHARGE
![]()
DISCHARGE
UPS
INVERTER
AC |
|
SWITCH | AC OUTPUT |
| |
BYPASS |
|
STEP 3
Please wait until procedure is completed.
Note
To change from Bypass to UPS supply, follow the Startup Procedures - STEP 5.
If the AC switch does not function, contact Toshiba or authorized representatives.
AC INPUT
BATTERIES
BYPASS INPUT
BYPASS
AC - Vo 208 V
AC - Io 50%
PRESS ‘UPS’ SWITCH
| UPS |
|
CONVERTER | INVERTER |
|
FLOAT CHARGE | AC |
|
EQUAL CHARGE |
| |
DISCHARGE | SWITCH | AC OUTPUT |
|
BYPASS
52 | G8000 Series with Isolated Output Installation and Operation Manual |