Toshiba G8000 operation manual Grounding Wire, Be sure to ground the UPS as specified

Page 41

11.3Grounding Wire

WARNING

Be sure to ground the UPS as specified.

Using the UPS without a proper ground will deteriorate the insulation, cause leakage of currents and electric shock.The resistance to ground should be less than or equal to 10 ohms.

The 100/150 kVA earth grounding bus is located inside, at the bottom-front of the unit. The 150 kVA earth grounding buss is accessable through either the bottom or top knockout panel.

Use a 2 AWG (or 38 mm2) or larger cable for the grounding wire. Run the grounding wire through the opening at the bottom, or alternately through the top if a 150 kVA unit.

The ground wire must have a crimp terminal with a 1/2” (12 mm) diameter bolt hole. The ground bus has a 33/64” (13 mm) bolt hole. The crimp terminal and ground bus should be connected together using a 7/16” (10 mm) diameter bolt.

100 kVA

150 kVA

Facility earth ground. Alternate ground wire routing through top knockout plate.

Ground bus

10 mm or

 

7/16” Bolt

 

12 mm or 1/2”

 

Terminal

2 AWG (38 mm2)

 

ground wire

Feed-through opening

To facility

earth ground

Ground bus

10 mm or

 

7/16” Bolt

 

12 mm or 1/2”

 

Terminal

2 AWG (38 mm)

 

ground wire

Feed-through opening

To facility

earth ground

Note: Use either the top or the bottom access for the ground wire to connect to the ground buss, but use only one ground wire.

Figure 11.7 - EARTH GROUND WIre

G8000 Series with Isolated Output Installation and Operation Manual

33

Image 41
Contents G8000 Series Page G8000 Series Qualified Personnel only Uninterruptible Power System UPS Toshiba’s Customer Support Center PurposeToshiba Customer Support Center Toshiba International CorporationTable of Contents Terminal Blocks, Terminal Bus, and Power Cables 11.3 Introduction Prohibited Symbol indicates do not take action General Safety InstructionsSymbols Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsKeep the area arround the UPS clean General MaintenanceTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Keep the Specified Clearance around the UPS Installation PrecautionsInstall the UPS in a controlled environment Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Perform wiring and connections with correct polarity Wiring/ConnectionConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screwsFor 100 and 150 kVA GND 150kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions150kVA UPS Exterior Dimensions Inches Do not expose the unit to vibration or shock exceeding 0.5G Transporting8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Qualified Personnel shall Maintenance PrecautionsQualified Personnel only Do not open or mutilate the batteries DisposalDo not dispose of the batteries in a fire Installation UPS Clearance UnpackingAnchor Bolts Breaker UPS WiringAC Input Bypass Input AC Output Battery Terminal Blocks, Terminal Bus, and Power CablesBlock Number Cable Size Tightening Torque 100 KVA 150 KVA Bottom Cable Knockout Plates 100 kVA External BreakersBe sure to ground the UPS as specified Grounding WireSignal Name Operation Control WiresConnection Between UPS, Battery Cabinet & Bypass Breaker Jumper Cable Between the Neutral Terminal & Ground BUS Grounding ConfigurationMechanical Specification UPS SpecificationsGeneral Specification Rated Capacity 150kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD IndicatorsAC-VO AC- I O 50% Normal DisplayVolt Freq .0Hz 50%BYP I/P-V Freq .0Hz AC I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIM09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesPerform the pre-operational check before operating the UPS Operation TypesPre-operational Check Step Startup ProceduresAC Vo 208 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Batt FAULT1 warning goes away Types of Errors TroubleshootingEmergency Power Off EPO 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesAC O/P UV Button functions LCD Scroll w/ faults or warningsRestoring UPS Operation Contact Toshiba in the event of malfunction or faultDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsPage Page Industrial Division