11.5Grounding Configuration
This section describes the grounding configuration to be used with this UPS.
A 2 AWG (or 38 mm2)
|
| Neutral | |||
Ground | Terminal | ||||
Bus |
|
|
| Jumper | |
|
|
| |||
|
|
|
|
| Cable |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FIGURE 11.9 - JUMPER CABLE BETWEEN THE NEUTRAL TERMINAL & GROUND BUS
Since the input source is a
The jumper cable should stay in place. See Figure 11.9 for the jumper cable location.
UPS Cabinet
Input Source
3f
3f
G
3f
3f
G
3 f | 3 f |
| |
N | To | ||
N | |||
G | G | LOAD | |
| |||
| Junper Cable |
| |
| remains in place |
|
FIGURE 11.10 - GROUNDING CONFIGURATION FOR NON-GROUNDED DELTA-INPUT
36 | G8000 Series with Isolated Output Installation and Operation Manual |