Toshiba G8000 operation manual Important Safety Instructions, Factory Authorized Personnel

Page 12

Be trained and authorized to safely energize, de-energize, ground, lockout/tagout circuits and equipment, and clear faults in accordance with established safety practices.

Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety practices.

Be trained in rendering first aid.

For further information on workplace safety visit www.osha.gov.

2.4Factory Authorized Personnel

Factory authorized personnel have been factory trained and certified to install, service, and repair the UPS. Contact the Toshiba Customer Support Center for assistance in locating the factory authorized personnel nearest you.

3 Important Safety Instructions

The following contains important instructions that should be followed during the installation, operation, and maintenance of the G8000 Series UPS.

Please refer to the battery manufacturer’s instructions for details on operating, maintaining and/or replacing the batteries for each system. Unauthorized personnel from batteries. Only a factory authorized representative with battery experience should perform service on batteries.

caution

Misuse of this equipment could result in personal injury and/or equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may come from the use of this equipment.

The UPS system input and output is NOT equipped with an over-current protection device, or an output disconnection at the AC output. The user should provide circuit breakers between the UPS AC input (or Bypass input) and the power sources and between the UPS output and the critical load input. The minimum device ratings are listed in Table 3.1.

TABLE 3.1 UPS MINIMUM DEVICE RATINGS

Capacity

Rated Output

Input Breaker Rating

Output Breaker Rating

100 kVA

208/120 Vac

480V-200 A

208V-350 A

150 kVA

208/120 Vac

480V-250 A

208V-600 A

The maximum operating ambient temperature should be 40 °C (104 °F). If the UPS is exposed to the same ambient temperature as the battery system, the maximum operating ambient temperature should be 32 °C (90 °F). Table 3.2 lists the nominal battery voltage.

TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE

Capacity

Nominal Voltage

Float Voltage

100 kVA

360 Vdc

405 V

150 kVA

360 Vdc

405 V

G8000 Series with Isolated Output Installation and Operation Manual

Image 12
Contents G8000 Series Page G8000 Series Qualified Personnel only Uninterruptible Power System UPS Purpose Toshiba’s Customer Support CenterToshiba Customer Support Center Toshiba International CorporationTable of Contents Terminal Blocks, Terminal Bus, and Power Cables 11.3 Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelImportant Safety Instructions Factory Authorized PersonnelSafety Precautions DisclaimerGeneral Maintenance Keep the area arround the UPS cleanTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionDo not transport, move, store, or place the UPS on its side Avoid vibration or shock exceeding 0.5GInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not install the UPS where water may fall on it Do not block air ventsInstallation Precautions Environment standardPage Wiring/Connection Perform wiring and connections with correct polarityConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screwsFor 100 and 150 kVA GND 150kVA UPS Warning Labels Weight and Dimensions Model Unit Shipping150kVA UPS Exterior Dimensions Inches Transporting Do not expose the unit to vibration or shock exceeding 0.5GTransporting By Crane 8.5 show examples of acceptable and unacceptable operationsTransporting By Forklift Transporting UPS by ForkliftOperating Precautions Storage/Operating EnvironmentPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation Unpacking UPS ClearanceAnchor Bolts UPS Wiring BreakerTerminal Blocks, Terminal Bus, and Power Cables AC Input Bypass Input AC Output BatteryBlock Number Cable Size Tightening Torque 100 KVA 150 KVA External Breakers Bottom Cable Knockout Plates 100 kVAGrounding Wire Be sure to ground the UPS as specifiedControl Wires Signal Name OperationConnection Between UPS, Battery Cabinet & Bypass Breaker Grounding Configuration Jumper Cable Between the Neutral Terminal & Ground BUSUPS Specifications General SpecificationMechanical Specification Rated Capacity 150kVA Electrical Specification Do not open the front coverOperator Interface UPS may not respond if the button press is too shortKey-Switch and Buttons Graphic display Panel KEY-SWITCH/OPERATING Buttons13.2 LCD/LED Indicators Graphic display Panel LCD/LED INDICAtorsLCD Indicators Name DescriptionNormal Display AC-VO AC- I O 50%Volt Freq .0Hz 50%AC I/P-V Freq .0Hz BYP I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIMFault Display 09-09-06LCD Scroll AbbreveationsEpo and Control Power supply operating switches Operating the UPSOperation Types Pre-operational CheckPerform the pre-operational check before operating the UPS Startup Procedures StepAC Vo 208 AC Io 50% Switch Power Supply UPS→Bypass Bypass LED is onStop Complete Shutdown DC-V 0 BATT-V 0 BATT-I 0 aChanging Between Float Charge and Equalize Charge Make sure that the Float Charge LED is onMake sure that the Batt FAULT1 warning goes away Troubleshooting Emergency Power Off EPOTypes of Errors Faults and Warnings Data Screen 09-09-06LCD Fault & Warning Displays Fault DisplayFault Messages Over HeatAC O/P UV LCD Scroll w/ faults or warnings Button functionsContact Toshiba in the event of malfunction or fault Restoring UPS OperationDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsPage Page Industrial Division