Toshiba G8000 operation manual UPS Wiring, Breaker

Page 37

11 UPS Wiring

Note: Always consult your local and NEC electrical codes for wiring, cabling, and circuit protection devices. requirements.

Figure 11.1 illustrates the external wiring of the G8000 UPS. See corresponding section to each wiring term.

Power cable connection at terminal blocks/buses and external breaker provision for the AC input/output, Bypass Input and DC input.

Earth ground wire at grounding terminal.

Control wire terminal TB1 (battery cabinet and bypass breaker)

Bypass 3f 3W

bypass

34w

AC Input bypass

3f 3W

breaker

AC Input

33W

Input

breaker

Ground

wire

< UpS >

 

 

 

Contactor + Thyristor

 

 

bypass

Input

 

Contactor

 

 

Contactor

 

 

rectifier

Inverter

Inverter

 

 

Contactor

Chopper

 

 

Charger

 

 

 

 

Tb1

DC input

battery breaker

< battery Cabinet >

output 3 4w

output

breaker

FIGURE 11.1 - EXTERNAL WIRING DIAGRAM

An external maintenance bypass may be installed in parallel with the UPS to allow servicing of the G8000 while maintaining power to the UPS load. Contact the Toshiba Customer Service for further information.

G8000 Series with Isolated Output Installation and Operation Manual

29

Image 37
Contents G8000 Series Page G8000 Series Qualified Personnel only Uninterruptible Power System UPS Toshiba’s Customer Support Center PurposeToshiba Customer Support Center Toshiba International CorporationTable of Contents Terminal Blocks, Terminal Bus, and Power Cables 11.3 Introduction Symbols General Safety InstructionsProhibited Symbol indicates do not take action Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsKeep the area arround the UPS clean General MaintenanceTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Install the UPS in a controlled environment Installation PrecautionsKeep the Specified Clearance around the UPS Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Perform wiring and connections with correct polarity Wiring/ConnectionConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screwsFor 100 and 150 kVA GND 150kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions150kVA UPS Exterior Dimensions Inches Do not expose the unit to vibration or shock exceeding 0.5G Transporting8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Qualified Personnel only Maintenance PrecautionsQualified Personnel shall Do not dispose of the batteries in a fire DisposalDo not open or mutilate the batteries Installation UPS Clearance UnpackingAnchor Bolts Breaker UPS WiringAC Input Bypass Input AC Output Battery Terminal Blocks, Terminal Bus, and Power CablesBlock Number Cable Size Tightening Torque 100 KVA 150 KVA Bottom Cable Knockout Plates 100 kVA External BreakersBe sure to ground the UPS as specified Grounding WireSignal Name Operation Control WiresConnection Between UPS, Battery Cabinet & Bypass Breaker Jumper Cable Between the Neutral Terminal & Ground BUS Grounding ConfigurationGeneral Specification UPS SpecificationsMechanical Specification Rated Capacity 150kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD IndicatorsAC-VO AC- I O 50% Normal DisplayVolt Freq .0Hz 50%BYP I/P-V Freq .0Hz AC I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIM09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesPre-operational Check Operation TypesPerform the pre-operational check before operating the UPS Step Startup ProceduresAC Vo 208 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Batt FAULT1 warning goes away Emergency Power Off EPO TroubleshootingTypes of Errors 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesAC O/P UV Button functions LCD Scroll w/ faults or warningsRestoring UPS Operation Contact Toshiba in the event of malfunction or faultDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsPage Page Industrial Division