Toshiba G8000 Restoring UPS Operation, Contact Toshiba in the event of malfunction or fault

Page 71

15.6Restoring UPS Operation

WARNING

Contact Toshiba in the event of malfunction or fault.

This UPS should be repaired only by factory authorized personnel. Servicing by untrained personnel may extend the fault or result in electric shock or personal injury.

Do NOT attempt to modify or relocate the UPS.

Electric shock, personal injury or fault may result if unauthorized personnel attempt to modify or relocate the UPS. Be sure to contact toshiba customer service if you need to modifify or relocate the UPS.

Do not open the front and/or rear panels.

The parts inside carry energy-high current. Touching them may result in electric shock, burns or fault.

The procedure to restore UPS operation is shown in Steps 1-2. The example shows the UPS restored after a trip fault occurred on inverter over current with the message “INV. OC.”

AC INPUT

BATTERIES

BYPASS INPUT

LED Key

- LED Off

- LED On

BYPASS

1 INV. OC

07-15-07 08:05:30

ANOTHER ITEM

 

UPS

CONVERTER

INVERTER

FLOAT CHARGE

AC

EQUAL CHARGE

DISCHARGE

SWITCH

BYPASS

STEP 1

Check the LCD screen.

Also check other fault data screens with scroll buttons graphic panel.

STEP 2

Contact Toshiba and follow the directions given by the service personnel.

AC OUTPUT

G8000 Series with Isolated Output Installation and Operation Manual

63

Image 71
Contents G8000 Series Page G8000 Series Qualified Personnel only Uninterruptible Power System UPS Toshiba International Corporation PurposeToshiba’s Customer Support Center Toshiba Customer Support CenterTable of Contents Terminal Blocks, Terminal Bus, and Power Cables 11.3 Introduction Prohibited Symbol indicates do not take action General Safety InstructionsSymbols Qualified Personnel Signal WordsFactory Authorized Personnel Important Safety InstructionsDisclaimer Safety PrecautionsDo not tilt the UPS more than 10 from upright position General MaintenanceKeep the area arround the UPS clean Transporting/UnpackingAvoid vibration or shock exceeding 0.5G Do not transport, move, store, or place the UPS on its sideInspection/Storage Keep the Specified Clearance around the UPS Installation PrecautionsInstall the UPS in a controlled environment Do not block air vents Do not install the UPS where water may fall on itEnvironment standard Installation PrecautionsPage Follow the torque criteria for tightening screws Wiring/ConnectionPerform wiring and connections with correct polarity Connect only one 1 ground wire to the earth ground terminalFor 100 and 150 kVA GND 150kVA UPS Warning Labels Model Unit Shipping Weight and Dimensions150kVA UPS Exterior Dimensions Inches Do not expose the unit to vibration or shock exceeding 0.5G Transporting8.5 show examples of acceptable and unacceptable operations Transporting By CraneTransporting UPS by Forklift Transporting By ForkliftStorage/Operating Environment Operating PrecautionsPage Qualified Personnel shall Maintenance PrecautionsQualified Personnel only Do not open or mutilate the batteries DisposalDo not dispose of the batteries in a fire Installation UPS Clearance UnpackingAnchor Bolts Breaker UPS WiringAC Input Bypass Input AC Output Battery Terminal Blocks, Terminal Bus, and Power CablesBlock Number Cable Size Tightening Torque 100 KVA 150 KVA Bottom Cable Knockout Plates 100 kVA External BreakersBe sure to ground the UPS as specified Grounding WireSignal Name Operation Control WiresConnection Between UPS, Battery Cabinet & Bypass Breaker Jumper Cable Between the Neutral Terminal & Ground BUS Grounding ConfigurationMechanical Specification UPS SpecificationsGeneral Specification Rated Capacity 150kVA Do not open the front cover Electrical SpecificationUPS may not respond if the button press is too short Operator InterfaceGraphic display Panel KEY-SWITCH/OPERATING Buttons Key-Switch and ButtonsGraphic display Panel LCD/LED INDICAtors 13.2 LCD/LED IndicatorsName Description LCD Indicators50% Normal DisplayAC-VO AC- I O 50% Volt Freq .0Hz32TIM AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz DC-V BATT-V BATT- I 0A09-09-06 Fault DisplayAbbreveations LCD ScrollOperating the UPS Epo and Control Power supply operating switchesPerform the pre-operational check before operating the UPS Operation TypesPre-operational Check Step Startup ProceduresAC Vo 208 AC Io 50% Bypass LED is on Switch Power Supply UPS→BypassStop DC-V 0 BATT-V 0 BATT-I 0 a Complete ShutdownMake sure that the Float Charge LED is on Changing Between Float Charge and Equalize ChargeMake sure that the Batt FAULT1 warning goes away Types of Errors TroubleshootingEmergency Power Off EPO 09-09-06 Faults and Warnings Data ScreenFault Display LCD Fault & Warning DisplaysOver Heat Fault MessagesAC O/P UV Button functions LCD Scroll w/ faults or warningsDo not open the front and/or rear panels Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not attempt to modify or relocate the UPSPage Page Industrial Division
Related manuals
Manual 80 pages 62.95 Kb Manual 1 pages 30.84 Kb