Siemens AS 235 appendix ES 100 K extension system

Page 45

This catalog is out of date, see note on page 1

ES 100 K extension system

 

Up to eight ES 100 K extension systems can be connected in

 

order to supplement the 6 I/O module slots in the AS 235 K

 

system (max. 4 systems per I/O bus). Extension of the AS 235

 

system by the ES 100 K extension system is also possible.

 

Each ES 100 K system has space for 13 I/O modules. The num -

 

ber of I/O modules per AS 235 K automation system can there-

 

fore be extended to 108 (104 slots in the ES 100 K + 4 slots in

1

￿the AS 235 K).

The extension systems can be connected with a cascade or radial configuration. The total cable length must not exceed 500 m.

An interface module 6DS1322-8AA is required for the coupling in both the basic system and the extension system. The interface module can be inserted into any slot for I/O modules in the AS 235 K and ES 100 K systems. Slot 1 should be preferably used, however.

Automation systems

ES 100 K

ES 100 K extension system

SV1 M

13 slots

for I/O modules

Process connection panel

E

The ES 100 K extension system is available for AC 230 V and DC 24 V. It consists of:

• ES 902 subrack, 15 U high

 

– For AC 230 V

C79451-A3260-A3

– For DC 24 V

C79451-A3260-A4

each with

 

power supply subrack,

 

13 slots for I/O modules,

 

process connection panel for I/O modules,

 

power supply system,

 

cable clamping rail with 10 clamps

 

• Power supply module SV1

 

For ES 100 K with AC 230 V

 

– AC 230 V / DC 24 V

C79451-A3260-A20

For ES 100 K with DC 24 V

 

– DC 24 V

C79451-A3260-A25

• Interface module for ES 100 K

6DS1 322-8AA

The subrack corresponds to the ES 902 packaging system and is 15 U high. It contains slots for the power supply module, an alarm logic module, and the interface module for ES 100 K and 13 I/O modules.

The subrack also contains a process connection panel with 576 pins 2.4 mm x 0.8 mm in the Maxi-Termi-Point system.

A power supply module is required for the extension system depending on the selected supply voltage of the ES 100 K:

C79451-A3260-A20 (AC 230 V) or

C79451-A3260-A25 (DC 24 V).

The same power supply modules are also used in the AS 235 K system.

The alarm logic module 6DS1 901-8AA can the ordered as an optional accessory. It monitors the 24-V voltages L+ and PM, the optionally used signal inputs for temperature monitoring, door contact, fan contact and spare contact, e.g. if the ES 100 K extension system is installed in a TELEPERM M standard cabinet and if cabinet messages are to be detected or cabinet alarm lamps are to be triggered.

An alarm detected in the ES 100 K system is not transmitted to the central processing unit of an AS 235 K automation system, however. Therefore it does not lead to the output of an alarm text on the process monitor.

1Interface module for ES 100 K

EPower supply unit for AC 230 V or 2 x DC 24 V

M Alarm logic module

Fig. 3/9 ES 100 K extension system, design

Interface module for ES 100 K

The interface module for ES 100 K links the I/O bus of the

AS 235 K basic system to the I/O bus of the ES 100 K extension system via a cable.

Interface modules for ES 100 K are required in the AS 235 K basic system and in the ES 100 K extension system.

The interface module inserted in the ES 100 K provides the DC 5 V supply required for the I/O bus.

I/O modules

Slots for up to 13 I/O modules are present in the ES 100 K extension system. In addition to the I/O modules of the TELEPERM M process control system, certain I/O modules of the TELEPERM ME process control system can also be used in the ES 100 K system.

Depending on the addressing volume of the I/O bus, up to eight ES 100 K extension systems with a total of 104 I/O modules can be operated with one AS 235 K system.

See Section 4 for the properties, functions and Ordering data of the I/O modules.

Siemens PLT 111 · 1999

3/21

Image 45
Contents Teleperm M Brief description IntroductionFunctions of the AS 235 system ConfiguringGeneral system data System dataTechnical data of automation systems Or user-configured with own System architecture ConfiguringPerformance characteristics TML language Operation and monitoringScope of performance Redundancy with AS 235 H Redundancy with the AS 235 H automation systemImportant note Standard function blocks ConfiguringStandard function blocks Blocks for analog and digital processingData blocks Blocks for signal exchange via CSType Designation Function For modules with Order No Driver blocks for I/O modulesDriver blocks for I/O modules with standardized display Driver blocks for configurable Teleperm ME I/O modulesOrganization blocks Output blocks for printer and process monitorSystem architecture Performance characteristics Summary of system properties Redundancy with AS 235 H Configuring Data blocks Driver blocks for I/O modules Driver blocks for configurable Teleperm ME I/O modules Output blocks for printer and process monitor AS 235 H Connection diagramsAS 235 K ES 100 KGeneral GeneralAS 235 automation system Basic cabinetBasic cabinet Basic unitExtension units Standard I/O devicesBus components Power supply componentsOrdering data Ordering data for basic cabinetAS 235 automation system Basic cabinetOptions for AS 235 basic Cabinet Options for basic cabinet6DS9 002-8BB See page 6/6Extension cabinet Extension cabinetExtension cabinet Options for AS 235 extension CabinetAS 235 H automation system AS 235 HAS 235 H automation system, design 6DS3 305-8BA Example of redundancy with Redundant process I/OsInterface modules for 20-m local bus N-AS AS 235 H automation system Options for AS 235 H basic Cabinet AS 235 H extension cabinet AS 235 H automation Ordering data for extension cabinetSystem Extension cabinet Options for AS 235 H exten Sion cabinetBasic system AS 235 KAS 235 K automation system Basic systemAS 235 K automation system, design Interface module for ES 100 KOrdering data for AS 235 K HousingAS 235 K automation SystemES 100 K ES 100 K extension systemES 100 K extension system Ordering data for ES 100 K ES 100 K extensionES 100 K options Standard cabinets and accessories Standard cabinets and accessoriesSystem cabinet accessories Standard cabinetsOrdering data for system cabinet accessories Configuring values for thermal load Permissible thermal loadingStandard cabinet with heat exchanger Technical data Standard cabinets IP 20 without heat exchangerDesign 12 Standard cabinet with heat exchanger Standard cabinets IP 54 with heat exchangerProcess connection systems Connections for process signal cablesProcess connection systems Process connection systemsConnection diagrams Connection diagrams for standard I/O devices to AS AS 235 KStandard I/O devices to AS 235 / AS 235 K Connection of personal computer Connection of personal computerConnection of process monitors and parallel monitors Connection of process monitors and parallel monitorsStandard I/O devices to AS 235 H Connection diagrams for standard I/O devices to AS 235 HConnection diagrams Connecting cable Plug Cable Max. cable Order No From Length Summary of connecting cablesSignal modules Function modulesProportioning Counter modules Summary Configurable I/O modules General technical dataLightning protection with distributed configuration Power supply, earthingModules from other systems Selection criteria for I/O modulesClosed-loop control modules Function modulesFunction modules Closed-loop control modulesSignal modules Signal modulesAnalog input and output modules Binary input and output modules Binary input and output modulesBinary input module, testable, 6DS1 618-8CA Binary output module with 16 relays, 6DS1 605-8BAProportioning and counter modules STRUK-AS 220 EA configuring programProportioning counter module, metering pulse input module Metering pulse input module with 8 channels, 6DS1 607-8ABModules which can be used on the I/O bus Modules which can be used on the I/O busExplanations for the column Remarks Explanations for the column Release6DS1 342-1BD With S5KE Test mode Mode of operationOperation unit PBT 65 process operation keyboardConfiguring unit Configuring keyboardConfiguring keyboard Mini floppy disk unit Mini floppy disk unitMini floppy disk unit 6DS3 900-8AE Floppy disksBus communication Application ApplicationLocal range Design Remote rangeSingle remote bus Connection distributor AV Connector board AF Remote busBus converter Ul Redundant remote busBus configurations Bus configurations, examplesApplication Other conditions Connecting cables Connecting cables Connecting cables for 20-m local busConnecting cables for remote bus Expansion units Central controllersSimatic S5 I/Os ET 100U Coupling of other systems Interface modules for coupling with other systems, summarySimatic S5 expansion units Parallel coupling with S5-115U I/O modulesParallel coupling with Simatic S5-115U I/O modules Digital input modules Simatic S5-115U I/O modules appropriate for couplingDigital output modules Digital input/output modulesParallel coupling with Simatic S5-135U/155U I/O modules Parallel coupling with S5-135U/155U I/O modulesSimatic S5-135U/155U I/O modules appropriate for coupling Interface module for Simatic S5 expansion units Interface module for Simatic S5 expansion unitsSimatic S5/S7 central controllers Serial coupling With Simatic S5/S7 central controllersSerial coupling with Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllersSerial coupling with Simatic S5 I/Os Simatic S5 I/Os / ET 100UExi modules ET 100U I/O modules appropriate for couplingInterface module for ET 100U Interface module for ET 100UOrdering of complete systems AS 235 standard configuration Ordering informationOrdering of options