Coupling with other systems

SIMATIC S5/S7 central controllers

Serial coupling

with SIMATIC S5/S7 central controllers

AS 235, AS 235 H, AS 235 K, ES 100 K

I/O bus

.

..

Channel 1

Channel 2

SIMATIC

central controllers

S5-115U/-135U/-155U

CP 524 /

CP 544

SIMATIC automation systems S7-400 / S7-300

Ascreened, four-conductor cable twisted in pairs is used for data transmission. The maximum distance between the interface module and the central controller is 1000 m. Data transfer is sequential via a coupling link with 20-mA current loop. The chan- nel-specific transmission rate can be adjusted in steps:

Transmission rate

Max. coupling line length

300, 600, 1200, 2400 bits/s

1000 m

4800 bits/s

500 m

9600 bits/s

300 m

 

 

Data transfer between the AS 235 central processing unit and the interface module 6DS1 333-8AB is handled via the S5KS and S5KE driver blocks in the automation system. The 3964 or

3964 R transmission procedure (selectable) is used for data

Interface module

CP 441-2 CP 341

6DS1 333-8AB

 

 

 

 

 

 

 

max. 1000 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 7/3 Coupling of automation systems with SIMATIC S5/S7 central controllers

Serial coupling with SIMATIC S5/S7 central controllers

￿In certain cases it may be advantageous to assign autonomous parts of an automation program to a subordinate automation level. There is less loading on the automation system, and valu- able calculation time can be saved. This is especially important in the case of automation tasks with short cycle times which may place a heavy loading on the calculation capacity of a proces- sor. Subordinate programs can also be developed and tested independently of other program sections.

The following are required to couple the AS 235, AS 235 H and AS 235 K automation systems to SIMATIC S5-115U, S5-135U and S5-155U central controllers and SIMATIC S7-300 and S7-400 automation systems:

interface module for

SIMATIC S5/S7 central controllers 6DS1 333-8AB

• Connecting cable

6DS8 137-8..

For SIMATIC S5:

CP 524 communications processor 1) 6ES5 524-3UA15 CP 544 communications processor1) 6ES5 544-3UA11

For SIMATIC S7-300:

CP 341 communications processor 2) 6ES7 341-1BH00-0AE0 with 20-mA (TTY) interface

For SIMATIC S7-400:

CP 441-2 communications

 

processor 2)

6ES7 441-2AA02-0AE0

transmission between the interface module and the SIMATIC S5/S7 central controller.

RK 512 is used as the protocol. The SIMATIC S5 sends or fetches the data by means of messages. The TELEPERM M interface module is the passive participant in the communica- tion. S7 central controllers operate with SEND/RECEIVE and S5 analog-value format.

Further information

Catalog ST 50

for SIMATIC S5 central controllers and CP 524/544 communications processors

Catalog ST 70

for SIMATIC S7 central controllers and

CP 341/441-2 communications processors

The interface module 6DS1 333-8AB can be inserted into any slots for I/O modules of an AS 235 automation system or an ES 100 K extension system. A SIMATIC S5/S7 central controller can be connected to each of its 2 channels.

1)See Catalog ST 50 for interface modules, parameterization tools and acces- sories

2)See Catalog ST 70 for interface modules, parameterization tools and acces- sories

7/8

Siemens PLT 111 · 1999

Image 85
Contents Teleperm M Brief description IntroductionFunctions of the AS 235 system ConfiguringGeneral system data System dataTechnical data of automation systems Or user-configured with own System architecture ConfiguringPerformance characteristics Operation and monitoring TML languageScope of performance Redundancy with the AS 235 H automation system Redundancy with AS 235 HImportant note Standard function blocks ConfiguringStandard function blocks Blocks for analog and digital processingData blocks Blocks for signal exchange via CSType Designation Function For modules with Order No Driver blocks for I/O modulesDriver blocks for I/O modules with standardized display Driver blocks for configurable Teleperm ME I/O modulesOrganization blocks Output blocks for printer and process monitorSystem architecture Performance characteristics Summary of system properties Redundancy with AS 235 H Configuring Data blocks Driver blocks for I/O modules Driver blocks for configurable Teleperm ME I/O modules Output blocks for printer and process monitor AS 235 H Connection diagramsAS 235 K ES 100 KGeneral GeneralAS 235 automation system Basic cabinetBasic cabinet Basic unitExtension units Standard I/O devicesBus components Power supply componentsOrdering data Ordering data for basic cabinetAS 235 automation system Basic cabinetOptions for AS 235 basic Cabinet Options for basic cabinet6DS9 002-8BB See page 6/6Extension cabinet Extension cabinetExtension cabinet Options for AS 235 extension CabinetAS 235 H automation system AS 235 HAS 235 H automation system, design 6DS3 305-8BA Example of redundancy with Redundant process I/OsInterface modules for 20-m local bus N-AS AS 235 H automation system Options for AS 235 H basic Cabinet AS 235 H extension cabinet AS 235 H automation Ordering data for extension cabinetSystem Extension cabinet Options for AS 235 H exten Sion cabinetBasic system AS 235 KAS 235 K automation system Basic systemAS 235 K automation system, design Interface module for ES 100 KOrdering data for AS 235 K HousingAS 235 K automation SystemES 100 K extension system ES 100 KES 100 K extension system ES 100 K extension Ordering data for ES 100 KES 100 K options Standard cabinets and accessories Standard cabinets and accessoriesSystem cabinet accessories Standard cabinetsOrdering data for system cabinet accessories Permissible thermal loading Configuring values for thermal loadStandard cabinet with heat exchanger Standard cabinets IP 20 without heat exchanger Technical dataDesign 12 Standard cabinet with heat exchanger Standard cabinets IP 54 with heat exchangerProcess connection systems Connections for process signal cablesProcess connection systems Process connection systemsConnection diagrams for standard I/O devices to AS AS 235 K Connection diagramsStandard I/O devices to AS 235 / AS 235 K Connection of personal computer Connection of personal computerConnection of process monitors and parallel monitors Connection of process monitors and parallel monitorsStandard I/O devices to AS 235 H Connection diagrams for standard I/O devices to AS 235 HConnection diagrams Connecting cable Plug Cable Max. cable Order No From Length Summary of connecting cablesFunction modules Signal modulesProportioning Counter modules Summary Configurable I/O modules General technical dataLightning protection with distributed configuration Power supply, earthingModules from other systems Selection criteria for I/O modulesClosed-loop control modules Function modulesFunction modules Closed-loop control modulesSignal modules Signal modulesAnalog input and output modules Binary input and output modules Binary input and output modulesBinary input module, testable, 6DS1 618-8CA Binary output module with 16 relays, 6DS1 605-8BAProportioning and counter modules STRUK-AS 220 EA configuring programProportioning counter module, metering pulse input module Metering pulse input module with 8 channels, 6DS1 607-8ABModules which can be used on the I/O bus Modules which can be used on the I/O busExplanations for the column Release Explanations for the column Remarks6DS1 342-1BD With S5KE Test mode Mode of operationOperation unit PBT 65 process operation keyboardConfiguring keyboard Configuring unitConfiguring keyboard Mini floppy disk unit Mini floppy disk unitMini floppy disk unit 6DS3 900-8AE Floppy disksBus communication Application ApplicationLocal range Remote range DesignSingle remote bus Connection distributor AV Connector board AF Remote busBus converter Ul Redundant remote busBus configurations, examples Bus configurationsApplication Other conditions Connecting cables Connecting cables for 20-m local bus Connecting cablesConnecting cables for remote bus Central controllers Expansion unitsSimatic S5 I/Os ET 100U Coupling of other systems Interface modules for coupling with other systems, summaryParallel coupling with S5-115U I/O modules Simatic S5 expansion unitsParallel coupling with Simatic S5-115U I/O modules Digital input modules Simatic S5-115U I/O modules appropriate for couplingDigital output modules Digital input/output modulesParallel coupling with Simatic S5-135U/155U I/O modules Parallel coupling with S5-135U/155U I/O modulesSimatic S5-135U/155U I/O modules appropriate for coupling Interface module for Simatic S5 expansion units Interface module for Simatic S5 expansion unitsSerial coupling With Simatic S5/S7 central controllers Simatic S5/S7 central controllersSerial coupling with Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllersSerial coupling with Simatic S5 I/Os Simatic S5 I/Os / ET 100UExi modules ET 100U I/O modules appropriate for couplingInterface module for ET 100U Interface module for ET 100UOrdering information Ordering of complete systems AS 235 standard configurationOrdering of options